Piston/orifice change kit installation – EMI S2HB User Manual

Page 9

Advertising
background image

www.enviromaster.com

9

multi-zone Heat Pump Condensing units

The system will support refrigerant runs

to the inside unit of up to 100' equivalent

feet with a 35' rise included. The units

are furnished with sweat connections and

are equipped with refrigerant valves and

MultI-zonE HEAt PuMP rEfrIgErAnt PIPIng InStAllAtIon

Schrader fittings for charging and taking

pressure readings. The following precau-

tions should be made:

• Be certain no burrs remain on the

fittings.

• Use only clean refrigeration tubing.
• Use tube benders to guard against

kinking.

• Avoid piping on wet and rainy days

and insulate suction line. Be certain

that plastic end caps remain in place

when inserting through wall openings.

Isolate tubing from transmitting vibra-

tion to the building or unit and avoid

contact with sharp edges. refrigera-
tion valves should be wrapped with
a wet rag "heat sink" to protect
valves while brazing.

inTerConneCTing TuBing SPeCS

S2HB, T2HB, T3HB, & T4HB models:

Nominal

Circuit

Capacity

Maximum

Length

Maximum

Lift

Liquid

Line

OD

Suction

Line

OD

9,000

100’

35’

1/4”

1/2”

12,000

100’

35’

1/4”

1/2”

18,000

100’

35’

3/8”

5/8”*

24,000

100’

35’

3/8”

3/4”

noTe: Refrigerant Piping Installation for all of the multi-zone heat pump models.

PiSTon/oriFiCe CHange KiT inSTallaTion

Air Handler

When a WLH24 or UNH24 air handler is matched with a T2HB or T3HB contain-

ing a 24,000 Btuh nominal capacity circuit, the air handler must have it’s stock

piston changed from 0.059 to 0.063.

A 24,000 Btuh nominal circuit

can be identified by the “4” in

the model number capacity field (i.e.

T2HBx4xx). Refer to the instructions sup-

plied with kit part number; 240006777.

model #

air Handler

Condenser

Btuh

Factory installed

Piston/Orifice Size

Field Changeover

Piston/Orifice Size

WLH24

or

UNH24

T2HB2400

T2HB8400

T2HB4400

T3HB9940

T3HB9240

T3HB2240

.059”

.063”

Note: T

his kit is only supplied with the above Heat Pump models.

* CAH24, UNH24, WLH24 Suction Connection size

is 3/4” O.D. and must bush down to 5/8” for 18,000

Btuh circuits at the indoor unit.

Circuit Designators: 9 = 9000 Btuh • 2 = 12000 Btuh • 8 = 18000 Btuh • 4 = 24000 Btuh

(ex. - 8400 consists of one 18000 Btuh compressor and one 24000 Btuh compressor)