ELECTRICAL SPECIFICATIONS • t2HB, t3HB, And t4HB - 208/230V - 60 HErtz 1 - PHASE

CAPACITY

FAN MTR

COMPRESSOR

TOTAL

AMPS MCA

HACR

BRKR

MIN

VOLT

AMPS

HP

CIRCUIT #1

CIRCUIT #2

CIRCUIT #3

CIRCUIT #4

RLA LRA RLA LRA RLA LRA RLA

LRA

T2HB

8800

1.8

0.33

5.4

36

5.4

36

12.6

14.0

15

197

8400

1.8

0.33

5.4

36

8.8

54

16.0

18.2

25

197

4400

1.8

0.33

8.8

54

8.8

54

19.4

21.6

30

197

2400

1.8

0.33

4.3

27

8.8

54

14.9

17.1

25

197

9800

1.8

0.33

3.4

23

5.4

36

10.6

12.0

15

197

T3HB

9990

1.8

0.33

3.4

23

3.4

23

3.4

23

12.0

13.0

15

197

9920

1.8

0.33

3.4

23

3.4

23

4.3

27

12.9

14

15

197

9980

1.8

0.33

3.4

23

3.4

23

5.4

36

14

15.4

20

197

9940

1.8

0.33

3.4

23

3.4

23

8.8

54

17.4

19.6

25

197

9220

1.8

0.33

3.4

23

4.3

27

4.3

27

13.8

14.9

15

197

9280

1.8

0.33

3.4

23

4.3

27

5.4

36

14.9

16.3

20

197

9240

1.8

0.33

3.4

23

4.3

27

8.8

54

18.3

20.5

25

197

2280

1.8

0.33

4.3

27

4.3

27

5.4

36

15.8

17.2

20

197

2240

1.8

0.33

4.3

27

4.3

27

8.8

54

19.2

21.4

30

197

2220

1.8

0.33

4.3

27

4.3

27

4.3

27

14.7

15.8

20

197

T4HB

9999

1.8

0.33

3.4

23

3.4

23

3.4

23

3.4

23

15.4

16.3

20

197

9992

1.8

0.33

3.4

23

3.4

23

3.4

23

4.3

27

16.3

17.4

20

197

9922

1.8

0.33

3.4

23

3.4

23

4.3

27

4.3

27

17.2

18.3

20

197

9222

1.8

0.33

3.4

23

4.3

27

4.3

27

4.3

27

18.1

19.2

20

197

2222

1.8

0.33

4.3

27

4.3

27

4.3

27

4.3

27

19

20.1

25

197

Circuit Designators: 9 = 9000 Btuh 2 = 12000 Btuh 8 = 18000 Btuh 4 = 24000 Btuh (ex. - 8400 consists of one 18000 Btuh

compressor and one 24000 Btuh compressor)

inTerConneCTing TuBing SPeCS

T2HB, T3HB, & T4HB models:

Nominal

Circuit

Capacity

Maximum

Length

Maximum

Lift

Liquid

Line

OD

Suction

Line

OD

9,000

100’

35’

1/4”

1/2”

12,000

100’

35’

1/4”

1/2”

18,000

100’

35’

3/8”

5/8”*

24,000

100’

35’

3/8”

3/4”

* CAH24, UNH24, WLH24 Suction Connection size

is 3/4” O.D. and must bush down to 5/8” for 18,000

Btuh circuits at the indoor unit.