EMI S2HB User Manual

Page 8

Advertising
background image

www.enviromaster.com

8

multi-zone Heat Pump Condensing units

5. with a screw

-

driver punch
out and remove

the knock-outs
in the low &

high Volt elec-
trical connec

-

tion box.

Note:

Power should be run to a

weather proof disconnect box usually

within 3 feet of the unit.

eleCTriCal Wiring

6. From the disconnect box

feed the high

Volt wires through a weather proof con-
duit and

run the power through the 7/8"

hole (from knock-out) in the unit’s electri-

cal box. Anchor with a strain relief fitting.

Refer to the wiring diagram.

7. Following the wiring diagram,

run wires

to the High Volt pigtail in the control box

and attach L1 and L2 connections. Also

run green wire to ground lug.

8. Check wiring diagram for the required num-

ber of low voltage wires to be run between
indoor and outdoor sections.

!

!

9. Connect the 24 Volt wiring matching color

to terminal block designation for each zone

as labeled. Refer to the wiring diagram on

the inside front panel of the condenser,

and also refer to the wiring diagram on the
indoor unit. Low

Volt interconnect should

be at least 18 AWG.

When connecting to the rear terminal strip

there are two approaches.

a) Using a long straight screw driver over

the top of the front terminal strip while

holding the wire with needle nose pliers

from below.

b) Remove the mounting screw (stubby

screwdriver), then pull the entire front

terminal strip forward, disengaging the

tab on left from slot. When finished,

reinsert terminal strip tab into slot and

reinstall mounting screw.

CauTion

Make sure that Low Volt wiring for each

circuit is connected to the matching

Low Volt wiring.

10. R

eplace the unit’s electric box cover and

the front panel and tighten screws

.

t2HB, t3HB, And t4HB InStAllAtIon InStructIonS SEctIon

High Volt

Low Volt

Knock-out

Mounting

Screw