Install sealed throat connector or

flashing to prevent leakage of room

air up through chimney.

DV Only: Before installing vent

liners, mark each liner on both

ends to designate which is the

intake and the exhaust.

Measure the height of the chimney

before hand and purchase the

appropriate kit. Never attempt to

over-stretch a flexible liner to

accommodate the height of the

chimney.

Any flue damper must be removed

or blocked permanently in the open

position.

The chimney must be clean, in

good working order and constructed

of non-combustible materials.

Make sure that all chimney

cleanouts are tightly fitting and will

not permit air to leak into the

chimney

�� �����

�� �����

Initial Installation

QUALIFIED INSTALLERS ONLY

V

ENTING

F

IREPLACE

I

NSERTS

:

The ENVIRO FOCUS may be installed and vented into any solid fuel fireplace that has been installed

in accordance with the National, Provincial/State and local building codes and has been constructed of

non-combustible materials.
An approved chimney liner and rain cap must be used. A throat connector or flashing must be installed

to ensure a tight seal, top performance, safety and efficiency. Carefully follow the manufacturer’s

instructions which accompany the chimney liner kit.
Remove the vent collar plate from the top of the insert and connect it securely with sheet metal screws

and/or hose clamps. Check for any tears in the liner at this point.
IMPORTANT: The screws that hold the vent collar plate in its approved position must be installed.

Figure 24: Installation of Focus DV and BV.