Gas line connection, Initial installation, Never use an open flame for leak testing – Enviro FOCUS EG31-118 User Manual

Page 19: Qualified installers only g

Advertising
background image

Initial Installation

QUALIFIED INSTALLERS ONLY

G

AS

L

INE

C

ONNECTION

:

Warning: Only persons licensed to work with gas piping may make the necessary gas connections to

this appliance.
Gas Line Connection:
•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating

in a 3⁄8” male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2)

installation code in Canada. In the US, gas installations follow either local codes or the current edition of

the National Fuel Gas Code ANSI Z223.1.
•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating

conditions and was determined independently of any installed system.

The appliance and its’ shut-off valves must

be disconnected from the gas supply piping

system during any pressure testing where

the pressure exceeds 1⁄2 psig (3.45 KPa) or

the valve will be damaged.
The unit must be isolated from the gas

supply piping system by closing its’

individual manual shut off valve during any

pressure testing of the gas supply piping

system at pressures equal to or less than

1⁄2 psig (3.45 KPa).
Always check for gas leaks with a soap

and water solution after completing

the required pressure test.

O

L I

T

P

TP

TH

TP

TH

IN

OU

T

H

I

LO

N

OF

O

F

LI

P

T O

��������

�������� ���

�����

�������� ���

������

����

����� ����������

�����

��� �������

����

TO TEST VALVE PRESSURES:

The pressure taps are located on the top right of

the valve.

• Turn set screw 1 turn counterclockwise to

loosen.

• Place 5/16 in (8 mm) I.D. hose over the

pressure taps.

• Check pressures using a manometer.

• When finished, release pressure, remove hose

and tighten set screw.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Figure 27: Fully Labeled Gas Valve.

Table 4: Pressure and BTU Information.

Main Burner

Natural Gas

(in W.C./KPa)

Propane Gas

(in W.C./KPa)

Orifice:

#38 DMS

#52 DMS

Manifold Press:

3.8 / 0.95

11.0 / 2.74

Min. Manifold Press: 1.1 / 0.27

2.7 / 0.67

Max. Supply Press:

7.0 / 1.74

13.0 / 3.28

Min. Supply Press:

5.0 / 1.24

12.0 / 2.98

Max. BTU Input:

30,000/ 8.8 KW∙h 28,500/ 8.2 KW∙h

Min. BTU Input:

15,000/ 4.4 KW∙h 14,000/ 4.1 KW∙h