Initial installation, Never use an open flame for leak testing – Enviro C-11089 User Manual

Page 27

Advertising
background image

27

TO TEST VALVE PRESSURES:

The pressure taps are located on the front side of the valve (see Figure 54 & 55).
1. Remove the door (refer to M

AINTENANCE

AND

S

ERVICE

- G

LASS

D

OOR

R

EMOVAL

), log set and ember

material, brick panels, burner tray, and the valve cover to access the valve (refer to M

AINTENANCE

A

ND

S

ERVICE

- R

EMOVING

V

ALVE

C

OVER

).

2. Turn set screw one (1) turn counter-clockwise to loosen.
3. Place

5

/

16

in (8 mm) I.D. hose over the pressure taps.

4. Check pressures using a manometer.
5. When finished, release pressure, remove hose and tighten set screw.
6. Re-install the valve cover, burner tray, brick panels (refer to S

ECONDARY

I

NSTALLATION

- I

NSTALLING

THE

B

RICK

P

ANELS

), log set and ember material (refer to S

ECONDARY

I

NSTALLATION

- L

OG

S

ET

AND

E

MBER

I

NSTALLATION

) and the glass door.

Always check for gas leaks with a soap and water solution after completing the required

pressure test.

Table 6: Orifice and Pressure Information.

Main Burner

Natural Gas

Propane Gas

Orifice:

#42 DMS

#54 DMS

Manifold Press:

4.0 W.C. (0.99 KPa)

10.0 W.C. (2.47 KPa)

Min. Manifold Press:

0.2 W.C. (0.05 KPa)

2.3 W.C. (0.57 KPa)

Max. Supply Press:

7.0 W.C. (1.74 KPa)

13.0 W.C. (3.28 KPa)

Min. Supply Press:

5.0 W.C. (1.24 KPa)

12.0 W.C. (2.96 KPa)

Max. Input:

26,600 BTU/hr

(7.79 KW)

21,300 BTU/hr

(6.24 KW)

Min. Input:

6,500 BTU/hr

(1.9 KW)

11,400 BTU/hr

(3.34 KW)

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Figure 54: Labeled Gas Valve.

Figure 55: Opening Inlet Pressure Tap on

Valve.

Initial Installation

QUALIFIED INSTALLERS ONLY