Trouble shooting – Enviro C-11089 User Manual

Page 37

Advertising
background image

37

Possible Cause

Solution

Spark will not light

the pilot after

repeatedly pressing

the spark ignitor.

Air in the pilot supply line.

• Purge the line or start ignition several times.

No spark at pilot burner

• Check spark gap.

• Check wiring connections to ignitor.

• Check for spark in location along cable.

Valve.

• Replace the valve.

Over tightened

thermocouple interrupter.

• Replace the valve and thermocouple interrupter.

Receiver

• Replace the receiver and reset the receiver’s

code, refer to M

AINTENANCE

A

ND

S

ERVICE

-

C

HANGING

R

EMOTE

H

ANDSET

C

ODE

.

Pilot is lit and

control continues

to spark. Valve

shuts off after 10 to

30 seconds. Valve

operates manually.

Receiver.

• Replace the receiver and reset the receiver’s

code, refer to M

AINTENANCE

A

ND

S

ERVICE

-

C

HANGING

R

EMOTE

H

ANDSET

C

ODE

.

Pilot is lit and

sparking stops. Valve

shuts off after 10 to

60 seconds. Valve

does not operate

manually.
Note: For manual

operation turn the

valve knob to the

manual

position

and hold the safety

magnet

open

with a pen for

approximately

60

seconds (see Figure

79).

Not

enough

voltage

generated

from

the

thermocouple or too much

resistance in the circuit.
Note: To find which part of

the circuit is causing the

problem, a checklist for

each application can be

prepared using an Excel

calculation available from

Mertik Maxitrol.
Possible parts are: ON-

OFF switch, Temperature

switches, Thermo current

connections, Receiver.

• Use a digital multimeter set in the mV range

and measure the voltage by connecting the test

leads to the spade connector. Spade connector

is located on the outer surface, directly beside

the magnet nut (see Figure 80). The available

voltage must be at least 5mV. The manufacturer

must specify the drop time for the application.

The drop time can be measured after the

thermocouple is heated.

Thermocouple.

• Replace the thermocouple.

Low inlet pressure.

• Confirm the regulator’s pressure and sizing.

Replace if necessary.

Valve.

• Replace the valve. Do not over tighten the

thermocouple interrupter.

BV Only: Spill switch at

the draft hood may have

tripped.

• Correct cause of trip and reset switch.

Trouble Shooting

Figure 80: Voltage

Across Valve’s Spade

Connector.

Figure 79: Valve’s Safety

Magnet.