14.7 Troubleshooting

14.7.1 Error Messages

See “Error Messages” on page 151 for information relating to error messages.

14.7.2 Common

Problems and Solutions

Analog Output Incorrect

Make certain of the type of Analog Output (voltage or current) that the channel is
equipped with; see “Identifying the Output Type” on page 135.

Use the

DIAGNOSTICS

->

DAC FULL SCALE

and

DIAGNOSTICS

->

DAC ZERO SCALE

menu items to

force the Analog Output to a known output. Then, adjust your readout device, panel
meter, PLC or data acquisition system to match.

Check the output selection jumpers; see “Output Selection” on page 135.

Check the “

DAC SETUP

->

DAC. ZERO-SCALE

” and “

DAC SETUP

->

DAC FULL-SCALE

” menu items.

Sensitivity to EMI/RFI

To obtain maximum immunity to electromagnetic or radio frequency interference,
make certain that the shield of the cable is connected to ground/earth only at the read-
out device. The shield of the cable should not be connected to the instrument.