Operation, Sequence of operation, Initiate – Honeywell RM7800G User Manual

Page 11: Standby, Prepurge, Ignition trials

Advertising
background image

RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

11

66-1085—04

g. Lockout Interlock opens during PREPURGE

(RM7840E,L).

h. Ignition/pilot valve/intermittent pilot valve terminal is

energized.

i.

Main valve terminal is energized.

j.

Internal system fault occurred.

k. Purge card is removed.

l.

Purge card is bad.

4. PILOT FLAME ESTABLISHING Period (PFEP):

a. Low Fire Switch opens.

b. Lockout Interlock opens (RM7840E,L).

c. Ignition/pilot valve/intermittent pilot valve terminal is

not energized.

d. Early spark termination terminal is energized after

five seconds.

e. No flame is present at the end of PFEP.

f. Main valve terminal is energized (RM7800G,M).

g. Internal system fault occurred.

h. Purge card is removed.

i.

Purge card is bad.

5. MAIN FLAME ESTABLISHING Period (MFEP):

a. Low Fire Switch Opens.

b. Lockout Interlock opens (RM7840E,L).

c. Ignition/pilot valve/intermittent pilot valve terminal is

not energized.

d. Main valve terminal is not energized.

e. No flame is present at the end of MFEP.

f. Internal system fault occurred.

g. Purge card is removed.

h. Purge card is bad.

6. RUN Period:

a. No flame is present.

b. Lockout Interlock opens (RM7840E,L).

c. Interrupted pilot valve terminal is energized

(RM7840G,M).

d. Main valve terminal is not energized.

e. Internal system fault occurred.

f. Purge card is removed.

g. Purge card is bad.

7. POSTPURGE Period:

a. Preignition Interlock does not close in five seconds

and opens after five-second time period.

b. Ignition/pilot valve/intermittent pilot valve terminal is

energized.

c. Main valve terminal is energized.

d. Internal system fault occurred.

e. Purge card is removed.

f. Purge card is bad.

OPERATION

Sequence of Operation

The RM7800/RM7840 has the following operating sequences,

see Fig. 2, 3, 4, and Table 6. The RM7800/RM7840 LED

provide positive visual indication of the program sequence:

POWER, PILOT, FLAME, MAIN and ALARM.

Initiate

The RM7800/RM7840 enters the INITIATE sequence when

the Relay Module is powered. The RM7800/RM7840 can also

enter the INITIATE sequence if the Relay Module verifies

voltage fluctuations of +10/-15 percent or frequency

fluctuations of +/-10 percent during any part of the operating

sequence. The INITIATE sequence lasts for ten seconds

unless the voltage or frequency tolerances are not met. When

the tolerances are not met, a hold condition is initiated and

displayed on the VFD for at least five seconds. When the

tolerances are met, the INITIATE sequence restarts. If the

condition is not corrected and the hold condition exists for four

minutes, the RM7800/RM7840 locks out. Causes for hold

conditions in the INITIATE sequence:

a. AC line dropout is detected.

b. AC line noise prevents a sufficient reading of the

line voltage inputs.

c. Low line voltage brownouts occur.

The INITIATE sequence also delays the burner motor starter

from being energized and de-energized from an intermittent

AC line input or control input.

Standby

The RM7800/RM7840 remains in standby, ready to start. The

operating control determines a call for heat is present and

provides input to terminal 6. The burner switch, limits,

operating control and all microcomputer monitored circuits

must be in the correct state for the RM7800/RM7840 to

advance into the PREPURGE sequence.

Prepurge

The RM7800/RM7840 provides a prepurge timing selectable

from two seconds to 30 minutes with power applied and the

RM7800 operating control indicating a call for heat:

a. Running Interlocks, Preignition Interlocks, Burner

Switch, Run/Test Switch, Lockout Interlocks and all

microcomputer monitored circuits must be in the

correct operating state.

b. The blower motor output, terminal 5, is powered to

start the PREPURGE sequence, except for the

RM7800E/RM7840E. The firing rate motor is driven

to the high fire position. The PREPURGE timing for

the RM7800/RM7840E,L does not begin until the

Lockout Interlock String and High Fire Switch are

both closed. The blower motor output for the

RM7800E is not energized until the High Fire Switch

is closed.

c. The Preignition Interlock input must remain closed

throughout PREPURGE; otherwise, control returns

to the STANDBY state and holds (30 seconds) for

the RM7800/RM7840G,M or safety shutdown for the

RM7800/RM7840E,L occurs.

d. The Lockout Interlock or Running Interlock inputs

(interlock circuit including Airflow Switch) must close

by ten seconds into PREPURGE; otherwise, a

recycle to the beginning of PREPURGE for the

RM7800/RM7840G,M will happen or a safety

shutdown for the RM7800/RM7840E,L occurs.

e. When PREPURGE timing is complete, the firing rate

motor drives to the low fire position,

RM7800/RM7840E,G,L.

f. When the firing rate motor reaches low fire position,

the Low Fire Switch, terminal 18, input must be

energized before entering the Ignition Trial state.

Ignition Trials

1. Pilot Flame Establishing Period (PFEP):

a. With the firing rate motor at the low fire position:

(1) The pilot valve and ignition transformer,

terminals 8, 10 and 21, are energized. The

RM7800M has an intermittent pilot valve,

Advertising
This manual is related to the following products: