RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

15

66-1085—04

Table 8. Static Checkout.

Test

No.

RM7800/

RM7840

Models

Test

Jumpers Voltmeter

Normal Operation

If Operation is Abnormal,

Check the Items Listed Below

1

All

None

4-L2

Line voltage at Terminal 4.

1. Master Switch.

2. Power connected to the Master Switch.

3. Overload protection (fuse, circuit breaker,

etc.) has not opened the power line.

2

6-L2

Line voltage at Terminal 6.

1. Limits.

2. Burner Controller.

3

20-L2

Line voltage at Terminal 20.

1. Preignition interlocks.

4

4-5

7-L2

1. Burner motor (fan or

blower) starts.

2. Line voltage at Terminal

7 within 10 seconds.

1. Burner motor circuit.

a. Manual switch of burner motor.

b. Burner motor power supply, overload

protection, and starter.

c. Burner motor.

2. Running or Lockout Interlocks (including

Airflow Switch).

5

4-10

Ignition spark (if ignition

transformer is connected to

Terminal 10)

1. Watch for spark or listen for buzz.

a. Ignition electrodes are clean.

b. Ignition transformer is okay.

6

All

4-8

1. Ignition spark (if ignition

transformer is connected to

Terminal 8).

2. Automatic pilot valve opens (if

connected to Terminal 8).

NOTE: Refer to wiring diagram of

system being tested.

1. Watch for spark or listen for buzz.

a. Ignition electrodes are clean.

b. Ignition transformer is okay.

2. Listen for click or feel head of valve for

activation.

a. Actuator if used.

b. Pilot valve.

7

4-21

Same as test no. 6 for connections

to Terminal 8. If using direct spark

ignition, check the first stage fuel

valve(s) instead of the pilot valve.

Same as test no. 6. If using direct spark

ignition, check the first stage fuel valve(s)

instead of the pilot valve.

8

4-9

Automatic main fuel valve(s) open.

If using direct spark ignition on a

model with intermittent pilot on

Terminal 21, check the optional

second stage fuel valve, if used.

1. Listen for and observe operation of the

main

fuel valve(s) and actuator(s).

2. Valve(s) and actuator(s).

9

4-3

Alarm (if used) turns on.

1. Alarm.

10

RM7800E,G,L;

RM7840E,G,L

4-5

and

12-13

18-L2

Firing rate motor drives open; zero

volts at Terminal 18 after motor

starts driving open.

1. Low Fire Start Switch.

2. Firing rate motor and transformer.

11

RM7800E,G,L;

RM7840E,G,L

4-5

and

14-13

18-L2

Firing rate motor drives closed; line

voltage at Terminal 18 after motor

is in Low Fire position.

1. Low Fire Start Switch.

2. Firing rate motor and transformer.

12

RM7800E,L;

RM7840E,L

4-5

and

12-13

19-L2

Firing rate motor drives open; line

voltage at Terminal 19 after motor

is in High Fire position.

1. High Fire Purge Switch.

2. Firing rate motor and transformer.

13

RM7800E,L;

RM7840E,L

4-5

and

14-13

19-L2

Firing rate motor drives closed;

zero volts at Terminal 19 after

motor starts driving closed.

1. Low Fire Start Switch.

2. Firing rate motor and transformer.

14

RM7800E,G,L;

RM7840E,G,L

15-13

1. Raise setpoint of Series 90

controller—firing rate motor

should drive toward open.

2. Lower setpoint of Series 90

controller—firing rate motor

should drive toward closed.

1. Series 90 Controller.

2. Firing rate motor and transformer.