RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

7

66-1085—04

Fig. 2. Wiring subbase and sequence for RM7800E,L/RM7840E,L.

RM7800/RM7840E,L

POWER

00

OPERATING
CONTROLS
AND
INTERLOCKS

BURNER

FLAME
SIGNAL

FIRING
RATE
MOTOR

INITIATE
(INITIAL
POWERUP
ONLY)

POWER

STANDBY

POWER

PREPURGE
HOLD
DRIVE TO
HIGH FIRE

PREPURGE
HOLD
DRIVE TO
LOW FIRE

POWER

PILOT

FLAME

MAIN

POWER

PFEP
10 SEC.
(4 SEC. IF
JR1 CLIPPED

PILOT

FLAME

MAIN

POWER

MFEP

PILOT

FLAME

MAIN

RUN

POWER

POSTPURGE

POWER

STANDBY

00

00

10

25

00

15

20

SWITCHING

MOTOR ACTION

BURNER/BLOWER MOTOR

IGN.

15 SEC. PILOT

LIMITS AND BURNER CONTROLLER CLOSED

LOCKOUT INTERLOCKS CLOSED

PREIGNITION INTERLOCK CLOSED

LOW FIRE SW.

SAFE START CHECK

FLAME PROVING

10 SEC. IGN./PILOT 8

10

5

5 SEC.

21

6

TO

7

TO

20

TO

5

18

TO

13

15

TO

13

12

TO

M12263D

INTERLOCK. CHECK

HIGH FIRE SW.

19

TO

13

14

TO

13

14

TO

5

4

6

L1

MAIN VALVE

9

FOR THE R7800/R7840E: THE HIGH FIRE SWITCH MUST BE WIRED CORRECTLY TO PERFORM ENERGY SAVING PURGE
FUNCTIONS. THE BURNER/BLOWER MOTOR DOES NOT START UNTIL THE HIGH FIRE SWITCH MAKES.

RM7800L1053, RM7840L1026: TERMINAL 21 PROVIDES INTERMITTENT PILOT FUNCTION.

1

2

2

1

1

TIMED
PREPURGE

POWER

FLAME

MAIN

PILOT

ALARM

POWER

FLAME

MAIN

PILOT

ALARM

ALARM

ALARM

ALARM

00

IC

PII

SSC

LED
DISPLAY

M12261C

G

L2

3

4

4

5

5

6

7

8

9

10

F

(L1)

13

14

15

16

17

18

19

20

21

22

12

LOCKOUT INTERLOCKS

(INC. AIR FLOW SWITCH)

MASTER

SWITCH

LOW FIRE

START SWITCH

5 SECOND IGNITION

(EARLY SPARK

TERMINATION)

MAIN FUEL VALVE(S)

BURNER

CONTROLLER/LIMITS

BURNER MOTOR

(BLOWER)

HIGH FIRE

COMMON

LOW FIRE

MODULATE

120V ALARM

10 SEC. INTERRUPTED

PILOT/IGNITION

PREIGNITION

INTERLOCK

SERIES 90

FIRING RATE

MOTOR

SERIES 90

CONTROLLER

FLAME DETECTOR

120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION AS REQUIRED.

RM7800/7840E ONLY: HIGH FIRE PURGE SWITCH
CONNECTED TO (L1), NOT .

SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS
FOR CORRECT WIRING.

DO NOT WIRE TO ANY UNUSED TERMINALS.

RM7840L1026, RM7800L1053 HAVE INTERMITTENT
PILOT VALVE FUNCTIONS.

FOR DIRECT SPARK IGNITION (OIL

OR GAS)

IGNITION

TRANSFORMER

2ND STAGE

FUEL VALVE

(OPTIONAL)

R

W

B

R

W

B

L1

(HOT)

L2

1

8

9

10

L2

Q7800

2

15 SEC.

INTERRUPTED

PILOT VALVE

2

5

1

3

4

5

3

HIGH FIRE

PURGE SWITCH