Final wiring check – Honeywell RM7800G User Manual

Page 3

Advertising
background image

RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

3

66-1085—04

a. Do not run high voltage ignition transformer wires in

the same conduit with the flame detector, Data

Controlbus Module™, or Remote Reset Module

wiring.

b. Do not route flame detector, Data Controlbus

Module™, or Remote Reset Module leadwires in

conduit with line voltage circuits.

c. Enclose flame detector leadwires without armor

cable in metal cable or conduit.

d. Follow directions in flame detector, Data Controlbus

Module™, or Remote Reset Module Instructions.

8. Keyboard Display Module (KDM): Because the KDM is

powered from a low voltage, energy limited source, it

can be mounted outside of a control panel if it is

protected from mechanical damage.

NOTE: A 13 Vdc power supply must be used any time more

than one Keyboard Display Module is used.

9. Maximum wire lengths follow:

a. RM7800/RM7840 leadwires—The maximum length

of leadwire is 300 feet to terminal inputs (Control,

Preignition Interlock, Running/Lockout Interlock,

High Fire Switch and Low Fire Switch).

b. Flame Detector leadwires—The maximum flame

sensor leadwire length is limited by the flame signal

strength.

c. Remote Reset leadwires—The maximum length of

wire is 1000 feet to a Remote Reset pushbutton.

d. Data Controlbus Module™—The maximum Data

Controlbus Module™ cable length depends on the

number of system modules connected, the noise

conditions and the cable used. The maximum length

of all Data Controlbus Module™ interconnecting

wire is 1000 feet.

10. Make sure loads do not exceed the terminal ratings.

Refer to the label on the RM7800/RM7840 or to the

ratings in Tables 3, 4 and 5.

Final Wiring Check

1. Check the power supply circuit. The voltage and

frequency tolerance must match those of the

RM7800/RM7840. A separate power supply circuit may

be required for the RM7800/RM7840. Add the required

disconnect means and overload protection.

2. Check all wiring circuits and complete the Static

Checkout, see Table 8, before installing the

RM7800/RM7840 on the subbase.

3. Install all electrical connectors.

4. Restore power to the panel.

Table 1. Recommended Wire Sizes and Part Numbers.

Application

Recommended Wire Size

Recommended Part Number(s)

Line voltage terminals

14, 16 or 18 AWG copper conductor, 600

volt insulation, moisture-resistant wire.

TTW60C, THW75C, THHN90C.

Keyboard Display Module (KDM)

22 AWG two-wire twisted pair with

ground, or five wire.

Belden 8723 shielded cable or equivalent.

Data ControlBus Module™

22 AWG two-wire twisted pair with

ground, or five wire.

Belden 8723 shielded cable or equivalent.

Remote Reset Module

22 AWG two-wire twisted pair, insulated

for low voltage.

13 Vdc full-wave rectified transformer

power input.

18 AWG wire insulated for voltages and

temperatures for given application.

TTW60C, THW75C, THHN90C.