RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

13

66-1085—04

• Lockout information (Lockout, Fault Code, Message and

Sequence).

The extreme right side of the first line is either blank or shows

a small arrow pointing to the second line followed by a

two-letter code (DI-Diagnostic Information, Hn-Fault History

Information, and EA-Expanded Annunciator). When the arrow

and two-letter code are displayed, it indicates the second line

is showing a selectable message submenu. The second line

displays selectable or preemptive messages.

A selectable message supplies information for flame strength,

system status indication, system or self-diagnostics and

troubleshooting.

A preemptive message has parentheses around the message

and supplies a detailed message to support the sequence

status information. A preemptive message can also be a

lockout message. A preemptive message replaces a

selectable message to support the sequence status

information. It also replaces a selectable message after 60

seconds if it or a lockout message is available.

Run/Test Switch

WARNING

Explosion Hazard.

Can cause serious injury or death.

Do not use the Run/Test switch during the Pilot Flame

Establishing Period for the RM7800/RM7840G,M

when using Direct Spark Function, because it turns on

the main gas valve, causing an accumulation of fuel in

the burner.

The Run/Test Switch is located on the top side of the

RM7800/RM7840, see Fig. 6. The Run/Test Switch allows the

burner sequence to be altered as follows:

1. In Prepurge Drive To High Fire Position, the Run/Test

Switch, when placed in the TEST position, holds in

PREPURGE with the firing rate motor in the High Fire

position.

2. In the measured PREPURGE sequence, the Run/Test

Switch, when placed in the TEST position, causes the

PREPURGE timing to stop. The firing rate motor is in

the High Fire position.

3. In Prepurge Drive to Low Fire position, the Run/Test

Switch, when placed in the TEST position, holds the

burner sequence in PREPURGE with the firing rate

motor in the Low Fire position.

4. In PFEP, the Run/Test Switch, when placed in the TEST

position, stops the timer during the first eight seconds

when a ten second PFEP is selected or during the first

three seconds when a four second PFEP is selected,

allowing pilot-turn-down test and other burner

adjustments to be made. This activates a fifteen second

flameout timer that permits pilot flame adjustment

without nuisance safety shutdowns. The Run/Test

Switch is ignored during PFEP for the RM7800/

RM7840E,L if Terminals 8 and 9 or 9 and 21 are

jumpered.

5. During Run, the Run/Test Switch, when placed in the

TEST position, drives the firing rate motor to the Low

Fire position.

NOTE: When RM7800/RM7840 is switched to the Test

mode, it stops and holds at the next Run/Test Switch

point in the operating sequence. Make sure that the

Run/Test Switch is in the RUN position before

leaving the installation.

SETTINGS AND ADJUSTMENTS

Selectable Site-Configurable
Jumpers

The RM7800/RM7840 has three site-configurable jumper

options, see Fig. 6 and Table 7. If necessary, clip the

site-configurable jumpers with side cutters and remove the

resistors from the Relay Module.

Fig. 6. Selectable site-configurable jumpers.

RUN/TEST SWITCH

NOTE: CONFIGURATION JUMPERS SHOWN FOR RM7800G/RM7840G.

SELECTABLE CONFIGURATION JUMPERS

M12301