15

RM7800M;

RM7840M with

open damper

contacts..

14-13

If damper motor is used, motor

drives damper open.

Damper motor.

16

RM7800M;

RM7840M with

open damper

contacts..

4-5

18-L2

If damper motor is used, motor

drives open; line voltage at

Terminal 18 after motor is in Low

Fire position.

1. Low Fire Start Switch.

2. Damper motor.

17

RM7800M;

RM7840M with

open damper

contacts..

4-5

and

4-13

18-L2

If damper motor is used, motor

drives open; zero volts at

Terminal 18.

1. Low Fire Start Switch.

2. Damper motor.

Final

All

CAUTION

Equipment Damage Hazard.

Improper wiring can damage equipment.

On completing these tests, open the master switch and remove all test jumpers from the

subbase terminal. Also remove bypass jumpers from the low fuel pressure limits (if used) to

prevent equipment damage.