RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

5

66-1085—04

Table 2. Recommended Grounding Practices.

Table 3. Terminal Ratings.

.

a

The relay module must have an earth ground providing a connection between the subbase and the control panel or the

equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an

internal short circuit. The relay module requires a low impedance ground connection to the equipment frame, which, in turn,

requires a low impedance connection to earth ground.

b

2000 VA maximum connected load to relay module assembly.

c

See tables 4 and 5.

Ground Type

Recommended Practice

Earth ground (subbase and relay module).

1. Use to provide a connection between the subbase and

the control panel of the equipment. Earth ground must be

capable of conducting enough current to blow the 20A fuse

(or breaker) in the event of an internal short circuit.

2. Use wide straps or brackets to provide minimum length,

maximum surface area ground conductors. If a leadwire

must be used, use 14 AWG copper wire.

3. Make sure that mechanically tightened joints along the

ground path are free of nonconductive coatings and pro-

tected against corrosion on mating surfaces.

Signal ground (KDM, Data ControlBus Module™

Use the shield of the signal wire to ground the device to the

signal ground terminals [3(c)] of each device. Connect the

shield at both ends of the chain to earth ground.

Terminal No.

Description

Ratings

G

Flame Sensor Ground

a

Earth G

Earth Ground

a

L2(N)

Line Voltage Common

3

Alarm

120 Vac, 1A pilot duty.

4

Line Voltage Supply (L1)

120 Vac (+10%/-15%), 50 or 60 Hz (±10%)

b

5

Burner Motor

120 Vac, 9.8 AFL, 58.8 ALR (inrush).

6

Burner Controller and Limits

120 Vac, 1 mA.

7

Lockout/Running Interlock

120 Vac, 8A run, 43A inrush.

8

Pilot Valve/Ignition

120 Vac

c

.

9

Main Fuel Valve

120 Vac

c

.

10

Ignition

120 Vac

c

.

F(11)

Flame Sensor

60 to 220 Vac, current limited.

12

Firing Rate High Fire

120 Vac, 75 VA pilot duty.

13

Firing Rate Common

120 Vac, 75 VA pilot duty.

14

Firing Rate Low Fire

120 Vac, 75 VA pilot duty.

15

Firing Rate Modulate

120 Vac, 75 VA pilot duty.

16

Unused

17

Unused

18

Low Fire Switch Input

120 Vac, 1 mA.

19

High Fire Switch Input

120 Vac, 1 mA.

20

Preignition Interlock Input

120 Vac, 1 mA.

21

Interrupted/Intermittent Pilot Valve/First Stage Oil Valve

120 Vac

c

.

22

Shutter

120 Vac, 0.5A.