SAFETY SHUTDOWN

Safety Shutdown (Lockout) occurs if
any of the following occur during the
indicated period:

1. INITIATE Period:

a. Purge card is not installed or is removed.

b. Purge card is bad.

c. Configuration jumpers are changed (after 200 hours

of operation).

d. Ac line power errors occurred, see Operation

section.

e. Four minute INITIATE period has been exceeded.

2. STANDBY Period:

a. Flame signal is present after 240 seconds.

b. Preignition Interlock is open an accumulative time

of 30 seconds.

c. Interlock check feature is enabled and the

Interlock String (including airflow switch) is closed

for 120 seconds with controller closed.

d. Ignition/pilot valve/intermittent pilot valve terminal is

energized.

e. Main valve terminal is energized.

f. Internal system fault occurred.

g. Purge card is not installed or is removed.

h. Purge card is bad.

3. PREPURGE Period:

a. Preignition Interlock opens anytime during

PREPURGE period (RM7840E,L).

b. Flame signal is detected after first ten seconds

during PREPURGE (RM7840E,L).

c. High Fire Switch fails to close within four minutes

and fifteen seconds after the firing rate motor is

commanded to drive to the high fire position at the

start of PREPURGE (RM7840E,L).

d. Low Fire Switch fails to close within four minutes

and fifteen seconds after the firing rate motor is

commanded to drive to the low fire position at the

end of PREPURGE.

e. Running Interlock does not close within 30 seconds

(RM7840G,M).

f. Lockout Interlock does not close within 10 seconds

(RM7840E,L).

HONEYWELL

POWER
PILOT
FLAME
MAIN
ALARM

RESET

KEYBOARD
DISPLAY
MODULE
(STANDARD ON
RM7800E,G,L,M)

PURGE
TIMER

WIRING
SUBBASE

CAPTIVE
MOUNTING
SCREW

RUN/TEST
SWITCH

CONFIGURATION
JUMPERS

RELAY
MODULE

SEQUENCE
STATUS
LED PANEL

RESET
BUTTON

FLAME
AMPLIFIER

SCROLL

MODE

- SAVE -