RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

66-1085—04

14

Table 7. Site Configurable Jumper Options.

a

Pilot Valve /First Stage Oil Valve (Valve/Start) Terminal 21.

b

A 30 second MFEP can be accomplished by adding a jumper wire between Terminals 19 and 5.

SERVICE NOTE:Clipping and removing a site-configurable jumper enhances the level of safety. Removal after 200 hours of

main valve operation will result in a hard lockout, Code 110.

STATIC CHECKOUT

After checking all wiring, perform this checkout before

installing the RM7800/RM7840 on the subbase. These tests

verify the Q7800 Wiring Subbase is wired correctly, and the

external controllers, limits, interlocks, actuators, valves,

transformers, motors and other devices are operating

properly.

WARNING

Explosion and Electrical Shock Hazard.

Can cause serious injury, death or equipment

damage.

1. Close all manual fuel shutoff valve(s) before starting

these tests.

2. Use extreme care while testing the system. Line

voltage is present on most terminal connections

when power is on.

3. Open the master switch before installing or

removing a jumper on the subbase.

4. Before continuing to the next test, be sure to

remove test jumper(s) used in the previous test.

5. Replace all limits and interlocks that are not

operating properly. Do not bypass limits and

interlocks.

CAUTION

Equipment Damage Hazard.

Improper testing can damage equipment.

Internal surge protectors can break down and conduct

a current, causing the RM7800/RM7840 to fail the

dielectric test or possibly destroy the internal lightning

and high current protection. Do not perform a dielectric

test with the RM7800/RM7840 installed.

Equipment Recommended

1. Voltmeter (1M ohm/volt minimum sensitivity) set on the

0-300 Vac scale.

2. Two jumper wires; no. 14 wire, insulated, 12 inches

(304.8 mm) long with insulated alligator clips at both

ends. An ammeter may be used in place of a jumper

wire to check the amp usage when testing the blower

motor, ignition, pilot and main valve operation.

General Instructions

1. Perform all applicable tests listed in Static Checkout,

Table 8, in the order listed.

2. Make sure all manual fuel shutoff valve(s) are closed.

3. Perform only those tests designated for the specific

RM7800/RM7840 model being tested.

4. Raise the setpoint of the operating controller to simulate

a call for heat.

5. For each test, open the master switch and install the

jumper wire(s) between the subbase wiring terminals

listed in the Test Jumpers column.

6. Close the master switch before observing operation.

7. Read the voltage between the subbase wiring terminals

listed in the Voltmeter column.

8. If there is no voltage or the operation is abnormal, check

the circuits and external devices as described in the last

column.

9. Check all wiring for correct connections, tight terminal

screws, correct wire, and proper wiring techniques.

Replace all damaged or incorrectly sized wires.

10. Replace faulty controllers, limits, interlocks, actuators,

valves, transformers, motors and other devices as

required.

11. Make sure normal operation is obtained for each

required test before continuing the checkout.

12. After completing each test, be sure to remove the test

jumper(s).

WARNING

Explosion Hazard.

Can cause serious injury or death.

Make sure all manual fuel shutoff valves are closed

before performing static checkout.

Jumper Number

Description

Intact

Clipped

RM7800/RM7840 Type

JR1

Pilot Flame Establishing

Period (PFEP)

10 seconds

4 seconds

All

JR2

Pilot Valve

a

/Main Flame

Establishing Period (MFEP)

10 seconds

Intermittent

15 or 30 seconds Interrupted

b

RM7800G/RM7840G

JR3

Start-up Interlock Check

Disabled

Enabled

All