RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

66-1085—04

2

WARNING

Electrical Shock Hazard.

Can cause serious injury or death.

Disconnect the power supply before beginning

installation. More than one power supply disconnect

may be required.

IMPORTANT

1. Wiring connections for the relay modules are unique;

therefore, refer to Fig. 2, 3, 4, or the correct

Specifications for proper subbase wiring, and

sequence charts.

2. Wiring must comply with all applicable codes,

ordinances and regulations.

3. Wiring must comply with NEC Class 1 (Line Voltage)

wiring.

4. Loads connected to the RM7800/RM7840 must not

exceed those listed on the RM7800/RM7840 label or

the Specifications, see Table 1.

5. Limits and interlocks must be rated to simultaneously

carry and break current to the ignition transformer,

pilot valve, and main fuel valve(s).

6. All external timers must be listed or component

recognized by authorities who have jurisdiction for

the specific purpose for which they are used.

7. For on-off gas-fired systems, some authorities who

have jurisdiction prohibit the wiring of any limit or

operating contacts in series between the flame

safeguard control and the main fuel valve(s).

8. Two Flame Detectors can be connected in parallel

with the exception of Infrared Flame Detectors

(C7015, C7915), Ultraviolet Flame Detectors

(C7927, C7961) or Visible Light Detector (C7962).

9. This equipment generates, uses and can radiate

radio frequency energy and, if not installed and used

in accordance with the instructions, may cause

interference to radio communications. It has been

tested and found to comply with the limits for a

Class B computing device of Part 15 of FCC rules

which are designed to provide reasonable protection

against such interference when operated in a

commercial environment. Operation of this

equipment in a residential area may cause

interference; in which case, the users at their own

expense may be required to take whatever

measures are required to correct this interference.

10.This digital apparatus does not exceed the Class B

limits for radio noise for digital apparatus set out in

the Radio Interference Regulations of the Canadian

Department of Communications.

Location

Humidity

Install the relay module where the relative humidity never

reaches the saturation point. The relay module is designed to

operate in a maximum 85 percent relative humidity

continuous, noncondensing, moisture environment.

Condensing moisture may cause a safety shutdown.

Vibration

Do not install the relay module where it could be subjected to

vibration in excess of 0.5G continuous maximum vibration.

Weather

The relay module is not designed to be weather tight.

When installed outdoors, protect the relay module using an

approved weather-tight enclosure.

Mounting Wiring Subbase

1. Mount the subbase in any position except horizontally

with the bifurcated contacts pointing down. The

standard vertical position is recommended. Any other

position decreases the maximum ambient temperature

rating.

2. Select a location on a wall, burner or electrical panel.

The Q7800 can be mounted directly in the control

cabinet. Be sure to allow adequate clearance for

servicing, installation, access or removal of the

RM7800/RM7840, Expanded Annunciator, Keyboard

Display Module, flame amplifier, flame amplifier signal

voltage probes, Run/Test Switch, electrical signal

voltage probes and electrical field connections.

3. For surface mounting, use the back of the subbase as a

template to mark the four screw locations. Drill the pilot

holes.

4. Securely mount the subbase using four no. 6 screws.

Wiring Subbase

WARNING

Electrical Shock Hazard.

Can cause serious injury, death or equipment

damage.

Disconnect the power supply before beginning

installation to prevent electrical shock, equipment

and control damage. More than one power supply

disconnect may be required.

1. For proper subbase wiring, refer to Figs. 2, 3, 4 or 5.

2. For proper remote wiring of the Keyboard Display

Module, through a 203541 5-wire Connector, refer to

the Specifications for the Keyboard Display Module

(65-0090), Data ControlBus Module™ (65-0091) or

Extension Cable Assembly (65-0131).

3. Disconnect the power supply from the main disconnect

before beginning installation to prevent electrical shock

and equipment damage. More than one disconnect may

be required.

4. All wiring must comply with all applicable electrical

codes, ordinances and regulations. Wiring, where

required, must comply with NEC, Class 1 (Line Voltage)

wiring.

5. Recommended wire size and type: see Table 1.

6. Recommended grounding practices: see Table 2.

The Keyboard Display Module and Data ControlBus Module™

(for remote mounting or communications), through a 203541

5-wire Connector, must be wired in a daisy chain

configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of

interconnection of all the devices listed above is not important.

Be aware that modules on the closest and farthest end of the

daisy chain configuration string require a 120 ohm (1/4 watt

minimum) resistor termination across terminals 1 and 2 of the

electrical connectors, for connections over

100 feet.

7. Recommended wire routing of leadwires: