RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES

66-1085—04

6

Table 4. Combinations for Terminals 8, 9, 10 and 21.

Table 5. Explanation of Each Combination.

Mounting RM7800/RM7840
Relay Module (Fig. 5)

1. Mount the RM7800/RM7840 vertically on the Q7800

Subbase, or mount horizontally with the knife blade

terminals pointing downward. When mounted on the

Q7800A, the RM7800/RM7840 must be in an electrical

enclosure.

2. When mounting in an electrical enclosure, provide

adequate clearance for servicing, installation and

removal of the RM7800/RM7840, Keyboard Display

Module, flame amplifier, flame amplifier signal voltage

probes, electrical signal voltage probes, and electrical

connections.

a. Allow an additional two inches below the

RM7800/RM7840 for the flame amplifier mounting.

b. Allow an optional three-inch minimum to both sides

of the RM7800/RM7840 for electrical signal voltage

probes.

3. Make sure no subbase wiring is projecting beyond the

terminal blocks. Tuck in wiring against the back of the

subbase so it does not interfere with the knife blade

terminals or bifurcated contacts.

IMPORTANT

The RM7800/RM7840 must be installed with a

plug-in motion rather than a hinge action.

4. Mount the RM7800/RM7840 by aligning the four

L-shaped corner guides and knife blade terminals with

the bifurcated contacts on the wiring subbase and

securely tighten the two screws without deforming the

plastic.

Pilot Fuel 8

Main 9

Ignition 10

Intermittent Pilot Valve 21

C

F

No Load

No Load

B

F

No Load

No Load

No Load

F

No Load

B

F

F

A

No Load

No Load

F

A

F

D

F

A

No Load

No Load

D

A

D

D

D

A

No Load

No Load

D

A

D

A

B

C

D

F

4.5A ignition.

50 VA Pilot Duty plus

4.5A ignition.

180 VA ignition plus

motor valve with:

660 VA inrush, 360 VA

open, 260 VA hold.

2A Pilot Duty.

64 VA Pilot Duty plus motor

valves with:

3850 VA inrush, 700 VA

open, 250 VA hold.