Heat & Glo Fireplace 7000XLS User Manual

Page 12

Advertising
background image

16

B. Installing Vent Components

The glass must be taken off again for positioning the logs

when the unit is finally installed in place and finished around

it. Re-install the glass door. Attach vent system to the top

starting collars.

1. Attach the First Vent Component to the

Starting Collars
To attach the first vent component to the starting collars

of the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the 5 inch (127mm) fireplace starting collar.

• Make sure that the fireplace rope gasket supplied with

the fireplace seals between the first 8-5/8 inch (219mm)

vent component and the outer fireplace wrap.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior

beads into the fireplace collar or previously installed com-

ponent end with four (4) equally spaced indented sections.

• When the internal beads of each 8-5/8 inch (219mm)

outer pipe line up, rotate the pipe section clockwise about

one-quarter (1/4) turn. The vent pipe is now locked together.

• The first 90° elbow installed in the vent system of a rear

venting fireplace MUST BE in a vertical position.

!

Figure 10. Attaching the First Vent Component

to the Starting Collars

WARNING: A 3/8 INCH (9.5 MM) BEAD OF

STOVE CEMENT MUST BE PLACED AROUND

THE 5 INCH (127 MM) FIREPLACE STARTING COL-

LAR BEFORE ATTACHING THE FIRST VENT COM-

PONENT. FAILURE TO SEAL THIS JOINT MAY

CAUSE THE FIREPLACE TO OPERATE IMPROPER-

LY. SEE THE DIAGRAM .

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

FIRST VENT

COMPONENT

!

WARNING: ENSURE THAT THE FIBER-

GLASS ROPE GASKET SUPPLIED WITH

THE FIREPLACE SEALS BETWEEN THE FIRST

VENT COMPONENT AND THE OUTER FIREPLACE

WRAP.

If the installation is for a termination cap attached directly

to the fireplace, skip to the sections, Install Firestops and

Vent Termination.