Section 3: installing the fireplace, Installing the fireplace – Heat & Glo Fireplace 7000XLS User Manual

Page 7

Advertising
background image

11

3

Installing the Fireplace

Step 1. Locating the Fireplace

The diagram below shows space and clearance require-

ments for locating a fireplace within a room.

A

B

C

D

E

42”

22”

36”

51”

72”

Minimum Clearances

from the Fireplace to Combustible Materials

Inches

mm

Glass Front ........................ 36 .................... 914

Floor ................................... 0 ....................... 0

Rear ...................................1/2 ..................... 13

Sides .................................1/2 ..................... 13

Top ................................... 3 1/2 ................... 89

Ceiling* .............................. 31 .................... 787

Figure 2. Fireplace Dimensions, Locations,

and Space Requirements

Clearance Requirements

The top, back, and sides of the fireplace are defined by

stand-offs. The minimum clearance to a perpendicular wall

extending past the face of the fireplace is one inch (25 mm).

The back of the fireplace may be recessed 21 1/2 inches

(546 mm) into combustible construction.

Framing should be

constructed of 2 X 4

lumber or heavier.

A. ............... 42”
B. ......... 38 1/2”
C. ............... 22”
D. ......... 25 5/8”

Figure 3. Framing Dimensions

For minimum clearances, see the direct vent termination

clearance diagrams on pages 19 and 20 in this manual.

Step 2. Framing the Fireplace

Fireplace framing can be built before or after the fireplace is

set in place. Framing should be positioned to accommo-

date wall coverings and fireplace facing material. The dia-

gram below shows framing reference dimensions.

CAUTION: MEASURE FIREPLACE DIMENSIONS AND

VERIFY FRAMING METHODS AND WALL COVERING

DETAILS BEFORE FRAMING.

Minimum Clearances

from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections. ............. 1 ................ 25
Horizontal Sections

Top ..................................... 3 ................ 75

Bottom ............................... 1 ................ 25

Sides ................................. 1 ................ 25
At Wall Firestops

Top .................................. 2 1/2 ............ 63.7

Bottom .............................. 1/2 ............... 13

Sides ................................. 1 ................ 25

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 28).

Shows center of 12” x 12” vent

framing hole for rear venting.

The center of the hole is one

inch (25.4mm) above the center

of the horizontal vent pipe.

A

B

C

The distance from the unit to combustible construction is to

be measured from the unit outer wrap surface to the com-

bustible construction, NOT from the screw heads that se-

cure the unit together.