For Vertical Runs - The vent system must be supported

every eight (8) feet (2.4m) above the fireplace flue outlet by

wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall

bracket to the framing members with nails or screws.

Figure 14. Installing Support Brackets

4. Install Firestops
For Horizontal Runs -
Firestops are REQUIRED on both

sides of a combustible wall through which the vent passes.
NOTE: Model DVK-01TRD does not need an exterior

firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through

either interior or exterior walls:
• Cut a 12-inch by 12-inch (305mm X 305mm) hole through

the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)

above the center of the horizontal vent pipe.

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 15. 12" x 12" Hole and Vent Pipe

Figure 16. Heat Shield, Interior & Exterior Firestops

VENT PIPE

1" (25.4 mm)

12"

(305mm)

12"

(305mm)

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

WALL BRACKET

WALL STUD

1 INCH MIN.

(25.4mm)

8 FT. (2.4m)

FLUE

OUTLET