Step 2. framing the fireplace – Heat & Glo Fireplace 36DV User Manual

Page 10

Advertising
background image

10

Framing should be
constructed of 2 X 4
lumber or heavier.

A. ......... 51-1/2”

B. ................ 46”

C. ................ 22”

D. ........55-1/8””

E. .......... 54-1/8”

Figure 3.

Framing Dimensions

Step 2. Framing the Fireplace

Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.

CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.

Shows center of 10” x 12” vent framing
holes for top and rear venting. The center
of the hole is one (1) inch (25.4mm) above
the center of the horizontal vent pipe.

B

C

A

D

E

Figure 4.

Clearance to an exposed combustible hearth extension

Figure 5.

Clearance to covered combustible hearth extension

12”

1”

MARBLE, GRANITE, TILE OR

OTHER NON-COMBUSTIBLE

HEARTH EXTENSION

WOOD OR OTHER COMBUSTIBLE

FLOOR OR PLATFORM

BOTTOM OF FIREPLACE

FRONT EDGE

OF ASH LIP

12”

FRONT EDGE

OF ASH LIP

NO COMBUSTIBLES

IN THIS ZONE

4”

BOTTOM

OF FIREPLACE

1” (BUILT INTO UNIT)

3” MIN.

WOOD OR OTHER

COMBUSTIBLE

FLOOR OR PLATFORM

MAY BE COMBUSTIBLE

MATERIAL

Clearance to Hearth Extension

If you want to use a non-combustible
hearth extension then the clearance
is reduced to 1 inch (25.4mm). See
Figure 5.

(4” Minimum to top surface of combustible floor or floor covering).