Step 9. wiring the fireplace – Heat & Glo Fireplace 36DV User Manual

Page 22

Advertising
background image

22

!

!

Wall Switch

You must use two wall switches with this unit. Position the
wall switch in the desired position on a wall. Run a maxi-
mum of 25 feet (7.8 m) or less length of 18 A.W.G. mini-
mum wire and connect it to the fireplace ON/OFF brown
switch wires.

WARNING: DO NOT CONNECT 110-120 VAC
TO THE WALL SWITCH OR THE CONTROL
VALVE WILL BE DESTROYED.

Wiring the Light

The light operates on 110-120 VAC. Position the wall switch
in the desired position on the wall. Connect 14 AWG mini-
mum wire to the black and white wires in the unit.

CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERA-
TION. VERIFY PROPER OPERATION AFTER SERVICING.

Intermittent Pilot Ignition (IPI) Wiring

3 Volt Transformer

This appliance comes with a 3 volt transformer found in the
manual bag. Plug the transformer leads to the green con-
trol module (see Figure 25). Then plug the transformer into
the “Trans” outlet on the junction box.

Appliance Requirements

This appliance requires that 110-120 VAC be wired to the
factory installed junction box. Maintain correct polarity when
wiring the junction box.

WARNING: DO NOT CONNECT 110-120 VAC
TO THE GAS CONTROL VALVE OR THE AP-
PLIANCE WILL MALFUNCTION AND THE
VALVE WILL BE DESTROYED
.

Optional Accessories

Optional remote control kits require that 110-120 VAC be
wired to the factory installed junction box before the fire-
place is permanently installed.

Heat-Zone kits are approved with this fireplace as heat
management accessories.

Multi-function wall switch (WSK-MLT) requires the PLUG-
ADP kit. Attach the black and white light wires to the plug
with two 1/4” electrical connectors. Plug the light into the
“AUX” cord on the WSK-MLT.

Step 9. Wiring the Fireplace

Figure 25. Intermittent Pilot Ignition (IPI) Wiring Diagram

NOTE 1: Ignition module, valve, pilot and wall switch operate on 3 volts.

NEUTRAL

GROUND

REMOTE

CONTROL

HOT

LOW VOLTAGE

SEE NOTE 1

ON/OFF

WALL SWITCH

VALVE

BROWN

BROWN

RED

ORANGE

GREEN

BLACK

OPTIONAL

BATTERY
BACK-UP

BLACK (IGNITOR)

BLACK (SENSOR)

BLACK

GROUND TO

FIREPLACE

CHASSIS

PILOT ASSEMBLY

AND VALVE ASSEMBLY

MUST BE GROUNDED

(COMMON GROUND

WITH FIREPLACE

CHASSIS)

SPARK TO

PILOT IGNITOR

IGNITOR

MODULE

3V

TRANSFORMER OUTLET

PLUG-IN

3V TRANSFORMER

FLAME SPARKER /

SENSOR

LOW VOLTAGE

SEE NOTE 1

OPTIONAL

BATTERY
BACK-UP

IGNITION

MODULE

(3V)

CONNECT TO LOW

VOLTAGE WALL SWITCH

TRANSFORMER

3V

BLACK

WHITE

Back light must be wired to a separate 110-120 VAC wall switch.