Step 3. installing the vent system – Heat & Glo Fireplace 36DV User Manual

Page 12

Advertising
background image

12

Figure 7.

Vent System Components and Termination Kits

Step 3. Installing the Vent System

A. Vent System Approvals

These models are approved to use DVP-series direct vent
pipe components and terminations (see Figures 6 and 7).
Approved vent system components are labeled for identifi-
cation. This pipe is tested and listed as an approved com-
ponent of the fireplace. The pipe is tested to be run inside
an enclosed wall. There is no requirement for inspection
openings at each joint within the wall. There is no required
pitch for horizontal vent runs. NO OTHER VENTING SYS-
TEMS OR COMPONENTS MAY BE USED
.

Detailed installation instructions are included with each vent
termination kit and should be used in conjunction with this
Installers Guide.

The flame and ember appearance may vary based on the type
of fuel burned and the venting configuration used.

Identifying Vent Components

The vent systems installed on this gas fireplace may in-
clude one, two, or three 90°

elbow assemblies. The rela-

tionships of vertical rise to horizontal run in vent configura-
tions using 90° elbows MUST BE strictly adhered to. The
rise to run relationships are shown in the venting drawings
and tables. Refer to the diagrams on the next several pages.

NOTE: Two 45° elbows may be used in place of one
90° elbow. Rise to run ratios in the vent system must
be followed if 45° elbows are used.

Terminations Kits

DVP-TV

PVK-80

DVP-TVHW

DVP-TRAP

DVP-TB1

(Required to have a minimum of 3
feet of vertical in the vent system)

HORIZONTAL
TERMINATION

WALL FIRESTOP

90 DEGREE
ELBOW

PIPE LENGTH

CEILING
FIRESTOP

VERTICAL
TERMINATION

STORM COLLAR

ROOF FLASHING