Heat & Glo Fireplace 36DV User Manual

Page 21

Advertising
background image

21

• At the gas line access hole, use insulation to re-pack

the space around the gas pipe.

• Insert insulation from the outside of the fireplace and

pack the insulation tightly to totally seal between the
pipe and the outer casing.

Step 7. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance
with local building codes by a qualified installer ap-
proved and/or licensed as required by the locality. (In
the Commonwealth of Massachusetts installation must
be performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch (13mm)
hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line. To install the gas supply line:

• A listed (and Commonwealth of Massachusetts approved)

1/2 inch (13mm) tee-handle manual shut-off valve and a
listed flexible gas connector are connected to the 1/2
inch (13mm) inlet of the control valve. NOTE: If substi-
tuting for these components, please consult local codes
for compliance.

• Locate the gas line access hole in the outer left-side

casing of the fireplace.

• Insert the gas line through the access hole. Position the

ball valve on the flex line to line up with the gas line.
Attach the gas line.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, use a soap

solution to carefully check all gas connections for leaks.

WARNING: DO NOT USE AN OPEN FLAME TO
CHECK FOR GAS LEAKS
.

!

Step 8. Gas Pressure Requirements

Pressure requirements for Heat-N-Glo gas fireplaces are
shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
Use a small flat blade screwdriver to crack open the screw
in the center of the tap. Position a rubber hose over the tap
to obtain the pressure reading.

The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).