Heat & Glo • PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI • 2005-900 Rev. K • 11/06

36

• Insert insulation from the outside of the fireplace and

pack the insulation tightly to totally seal between the
pipe and the outer casing.

• At the gas line access hole the gap between the supply

piping and gas access hole can be plugged with non-
combustible insulation to prevent cold air infiltration.

Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance
with local building codes by a qualified installer
approved and/or licensed as required by the locality.
(In the state of Massachusetts installation must be
performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch
(13 mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line.

To install the gas supply line:

• A listed (and State of Massachusetts approved) 1/2 inch

(13mm) tee-handle manual shut-off valve and a listed
flexible gas connector are connected to the 1/2 inch
(13mm) inlet of the control valve. NOTE: If substituting
for these components, please consult local codes for
compliance.

• Locate the gas line access hole in the outer casing of

the fireplace.

• The gas line may be run from either side of the fireplace

provided the hole in the outer wrap does not exceed 2” in
diameter and it does not penetrate the actual firebox.

• Open the fireplace lower grille, insert the gas supply line

through the gas line hole, and connect it to the shut-off
valve.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, all connec-

tions must be tightened and checked for leaks with a
commercially-available, non-corrosive leak check solu-
tion. Be sure to rinse off all leak check solution following
testing.

WARNING: DO NOT USE AN OPEN FLAME
TO CHECK FOR GAS LEAKS
.

!

Step 7. Gas Pressure Requirements

Pressure requirements for Heat & Glo gas fireplaces
are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.

The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).

Figure 33. Gas Supply Line

USE A WRENCH ON
SHUT-OFF VALVE
WHEN TIGHTENING
GAS LINE.

MANUAL

SHUT-OFF

VALVE

FLEX CONNECTOR

GAS VALVE

GAS LINE

ACCESS

CONTROL VALVE