Safety and warnings – Fisher & Paykel OR60 User Manual

Page 5

Advertising
background image

3

Electrical

This cooker is to be installed and connected to the electricity supply only by an authorised person.

If the installation requires alterations to the domestic electrical system, call a qualified
electrician. The electrician should also check that the electrical system is suitable for the
electricity drawn by the cooker.

The appliance must be connected to the mains, checking that the voltage corresponds to the
value given in the rating plate and that the electrical cable sections can withstand the load
specified on the plate.

A suitable disconnection switch must be incorporated in the permanent wiring, mounted and
positioned to comply with the local wiring rules and regulations. The switch must be of an
approved type installed in the fixed wiring and provide a 3 mm air gap contact separation in all
poles in accordance with the local wiring rules.

In Australia and New Zealand, a switch of the approved type with a 3 mm air gap must be

installed in the active (phase) conductor of the fixed wiring.

The switch must always be accessible.

The power supply cable must not touch any hot parts and must be positioned so that it does not
exceed 75

O

C at any point.

This cooker must be connected to a suitable double pole control unit adjacent to the cooker. No
diversity can be applied to this control unit.

To connect the cooker to the mains, do not use adapters, reducers or branching devices as they
can cause overheating and burning.

If the power supply cable is damaged, it must only be replaced by an authorised person.

The cooker must be connected to the power supply using V105 insulated cable.

The cooker must be earthed.

Power supply (models with gas cooktop)

OR60 four-function models: 230-240V~ 2460-2680W 50Hz

OR60 seven-function models: 220-240V~ 3100W 50Hz

Safety and warnings

Advertising