Map descriptor example 1 – sensor / module events – FieldServer FCI 7100 Series User Manual

Page 10

Advertising
background image

FS-8700-112 Gamewell-FCI 7100 Driver Manual

Page 10 of 20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.4

Map Descriptor Example 1 – Sensor / Module Events

This Map Descriptor will be used to store messages from Loop 1, Module 1 to 99. To store modules on more than one loop, a separate Map Descriptor needs
to be defined for each loop. Since the event type was set to ‘Alarm’, only ‘Alarm’ events will be stored. To store all events, change the ‘Event Type’ to ‘Any’.

Example:

F.S.E.C. :[CR][LF]
FIRST ALARM: UP STAIRS N. ENT Manual Station L1M21 00:37:28 01/01/99[CR][LF]

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name

, Data_Array_Name

, Data_Array_Offset

, Function

, Node_Name

, Event_Type

, Point_Type

, Relay/Loop/Zone_Number

, Address

, Length

, Clear_On_Reset

ModuleData1

, DA_MODULE

, 0

, Passive_Client

, Panel-01

, Alarm

, Module

, 1

, 1

, 99

, Yes

The driver will
clear the
1(=Length)
element of the
Data Array called
DA_Panel
starting at
offset=0 when a
Reset message is
received.

It is
recommended
that you allocate
unique MD
names.

The address
specifies the
starting Module
number and the
Length tells the
driver the range
of Modules.
In this example:
Module 1 to 99

Change this to
‘Sensor’ for
sensors.

In this example,
only Alarm events
will be stored.
Messages
reporting other
events will be
ignored unless
other Map
Descriptors are
defined.

Data Array name
and starting
location where
data should be
stored.

The driver listens
passively for
messages from
the Panel. It
cannot poll for
data.

The name of the
Node defined in
Section 5.2.

Advertising
This manual is related to the following products: