Appendix B. Troubleshooting

Appendix B.1. Driver Error Messages.

Message

Description

FCI7100:#1 FYI. Use a DA called <%s> to expose diagnostic info.,
FCI_7100_STATS_DA )

Refer to Appendix B.2

FCI7100:#2 FYI. Added Event Desc=<%s> Index=%d Categ=%d ,
new_event_desc

,

new_event_desc_index_value

,

new_event_desc_categ ) ;

Printed for your info only. No action required
if it confirms your expectations.

FCI7100:#3 Err. No space. Reject Event Desc=<%s> Index=%d ,
new_event_desc , new_event_desc_index_value ) ;

There is only space for 60 event types.

2

FCI7100:#4 FYI. Duplicate Event Desc=<%s>. , new_event_desc
) ;

You are adding an event type that already
exists. If you are updating the category,
ignore the message. Otherwise correct the
configuration file.

2

FCI7100:#5 FYI. Duplicate Event Desc=<%s>. , new_event_desc
) ;

FCI7100:#6 Err. Event Index=%d. Too big to set bit., drv_bd-
>event_index )

If the event index is greater than 64 then the
data cannot be stored as bits as only 64 bits
are reserved for events.

FCI7100:#7a Err. DA=%s too short. Rqd=%d, dt->buffer_name ,
offset );

The Map Descriptor in question has a length
and offset which makes it run past the end of
the Data Array. Message 7b is printed when
data is being stored as bits.

2

FCI7100:#7b Err. DA=%s too short. Rqd=%d, possible_md->data-
>buffer_name , offset );
FCI7100:#8 FYI. Reset was rcvd and processed! Stamped %s %s ,
drv_bd->time , drv_bd->date )

Printed for information only. No action
required.

FCI7100:#9 Err. Reset was ignored.

This message is printed when a reset was
received but the driver could not reset any
data. Ensure that 'Clear_on_Reset' is set to
'no' on all Map Descriptors.

FCI7100:#10 FYI. Reset of DA=%s Off=%d Len=%d, possible_md-
>data->buffer_name , possible_md->bxi_data_buffer_offset ,
possible_md->data_length );

Printed for information only. No action
required.

FCI7100:#11 Err. Cant reset DA=%s len=%d rqd=%d,
possible_md->data->buffer_name , da_get_length_in_items (
(DAH_TYP)

possible_md->data

)

,

possible_md-

>data_length+possible_md->bxi_data_buffer_offset );

The Map Descriptor in question has a length
and offset which makes it run past the end of
the Data Array.

2

FCI7100:#12a Err. No MD's to store message data.

A message arrived and the driver could not
find a place to store the data. If you are not
interested in the data then ignore the
message. Otherwise update the configuration
file.

2

FCI7100:#12b Err. No MD's to store message data."

FCI7100:#13 Err. Msg was ignored. MD Required for Storage.

2

Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.