Client side connection parameters, Client side node parameters – FieldServer FCI 7100 Series User Manual

Page 7

Advertising
background image

FS-8700-112 Gamewell-FCI 7100 Driver Manual

Page 7 of 20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5

CONFIGURING THE FIELDSERVER AS A GAMEWELL-FCI 7100 SERIES CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Gamewell-FCI Series 7100.

5.1

Client Side Connection Parameters

Section Title
Connections
Column Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8, R1-R2

1

Protocol

Specify protocol used

FCI_7100,

FCI_7100_series,

FCI7100

Baud*

Specify baud rate

1200 (Vendor Limitation)

Parity*

Specify parity

None (Vendor Limitation)

Data_Bits*

Specify data bits

8 (Vendor Limitation)

Stop_Bits*

Specify stop bits

1 (Vendor Limitation)


Example

// Client Side Connections

Connections
Port , Protocol

, Baud , Parity

P8

, FCI_7100 , 1200 , None

5.2

Client Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for node

Up

to

32

alphanumeric

characters

Node_ID*

When multiple panels are networked in an FCI
network the Node_ID is the panel number. Set the
Node_ID of the local panel to zero, and create one
Node descriptor for each panel setting the
Node_ID to the panel number.

In networked configurations,
specify whole numbers 0,1,2,3

Protocol

Specify protocol used

FCI_7100,

FCI_7100_series,

FCI7100

FCI_Reset_Action_Option* Only required for networked configurations.

Reset_by_any_Node,

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available