FS-8700-112 Gamewell-FCI 7100 Driver Manual

Page 9 of 20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Column Title

Function

Legal Values

Point_Type

This driver uses this parameter to determine the suitability of
a Map Descriptor when looking for a location to store data
from an incoming message.

Zone, Relay, Loop,
Sensor, Module,
Panel

Relay/Loop/Zone_Number

Ignored when the Point Type is ‘Panel’
Point Type = Relay 1..255
Point Type = Zone 1..8
Point Type = Loop 1..2
Point Type = Module 1..2
Point Type = Sensor 1..2

Whole Numbers
1, 2 , etc

Length

Each Map Descriptor defines storage locations for a series of
addresses. This parameter specifies the length of the series.

1,2,3 .etc
Whole numbers

Address*

This parameter is only considered for those Map Descriptors
whose ‘Event Type’ is Module or Sensor. It specifies the
starting module or sensor number. The length parameter
determines the range of the sensor/module numbers

1..99, -

Store_As*

Set this parameter to ‘Bit’ to have the driver use the primary
Data Array to store using the ‘Bit Storage’ Method.
These methods are described in Error! Reference source not
found.

Bit, Index_Value

DA_Bit_Name*

If the default ‘Store As’ is specified or if the parameter is
omitted then you can specify a secondary array using this
parameter - the driver will store event data as ‘Bit Storage’ in
the secondary array (and as ‘Index Values’ in the primary
array.) These methods are described in Error! Reference
source not found.

One of the Data
Array

Names

defined in Section
0

Clear_On_Reset*

If a reset if received you can prevent the driver resetting the
Data Array Points associated with the Map Descriptor by
specifying this parameter.

Yes, No