FS-8700-112 Gamewell-FCI 7100 Driver Manual

Page 17 of 20

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Message

Description

FCI7100:#36 Err. Too Short. Bytes=%d , conn->ux_iptr"

An event message is less than 80 bytes long. If
this error is repeated often it is possible that a
FCI firmware update as made the driver
unusable. Take a log and contact tech support.

Appendix B.2. Driver Stats Exposed.

In addition to the standard FieldServer operating statistics the driver exposes certain key stats in a Data Array if
required. A Server Side device can then monitor these stats.

Add the following to your configuration file to activate these stats.

// Expose Driver Operating Stats.

Data_Arrays

Data_Array_Name , Data_Format , Data_Array_Length
fci-7100-stats

, UINT32

, 200


The driver exposes stats based on a port handle. The offset specified in the table below must be added to the
handle number multiplied by 100. i.e. for port whose handle is 1 then the driver will store the 1

st

stat at

1+100*1=101.

Stat

Offset Description

#define FCI_7100_STAT_NO_PLACE_TO_STORE

1

Increments each time point data is received but
there is no Map Descriptor to store the data (any)

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_ZONE

2

Increments each time point data is received but
there is no Map Descriptor to store Zone data

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_RELAY

3

Increments each time point data is received but
there is no Map Descriptor to store Relay data

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_LOOP

4

Increments each time point data is received but
there is no MD to store the Loop data

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_SENSOR

5

Increments each time point data is received but
there is no MD to store the Sensor data

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_MODULE

6

Increments each time point data is received but
there is no MD to store the Module data

#define FCI_7100_STAT_EMPTY_MSG

7

Number of times that a message line was was zero
bytes long (excluding the terminator)

#define FCI_7100_STAT_SHORT_MSG

8

Number of times that a message line was was too
short probably a system id tag line

#define FCI_7100_STAT_NO_RESET

9

Increments each time a reset was rcvd but no DA
was reset

#define
FCI_7100_STAT_NO_PLACE_TO_STORE_PANEL

10

Increments each time point data is received but
there is no MD to store data that cannot be
attributed to a zone, relay, loop, sensor, module