Warning, Metering device, Compressor checks – Friedrich 2008 User Manual

Page 20

Advertising
background image

MeTeRING DeVICe

Capillary Tube Systems

All units are equipped with capillary tube metering

devices.
Checking for restricted capillary tubes.
1. Connect pressure gauges to unit.
2. Start the unit in the cooling mode. If after a few minutes

of operation the pressures are normal, the check valve

and the cooling capillary are not restricted.

3. Switch the unit to the heating mode and observe

the gauge readings after a few minutes running time.

If the system pressure is lower than normal, the heating

capillary is restricted.
4. If the operating pressures are lower than normal in

both the heating and cooling mode, the cooling

capillary is restricted.

locked Rotor Voltage (l.R.V.) Test

Locked rotor voltage (L.R.V.) is the actual voltage available

at the compressor under a stalled condition.

Single Phase Connections

Disconnect power from unit. Using a voltmeter, attach one

lead of the meter to the run “R” terminal on the compressor

and the other lead to the common “C” terminal of the com-

pressor. Restore power to unit.

Determine l.R.V.

Start the compressor with the volt meter attached; then stop

the unit. Attempt to restart the compressor within a couple

of seconds and immediately read the voltage on the meter.

The compressor under these conditions will not start and will

usually kick out on overload within a few seconds since the

pressures in the system will not have had time to equalize.

Voltage should be at or above minimum voltage of 197 VAC,

as specified on the rating plate. If less than minimum, check

for cause of inadequate power supply; i.e., incorrect wire

size, loose electrical connections, etc.

COMPReSSOR CHeCKS

ELECTRIC SHOCK HAZARD

WARNING

Turn off electric power before service or

installation. Extreme care must be used, if it

becomes necessary to work on equipment with

power applied.

Failure to do so could result in serious injury or

death.

Amperage (l.R.A.) Test

The running amperage of the compressor is the most impor-

tant of these readings. A running amperage higher than that

indicated in the performance data indicates that a problem

exists mechanically or electrically.

Single Phase Running and L.R.A. Test

NOTE: Consult the specification and performance section

for running amperage. The L.R.A. can also be found on the

rating plate.

Select the proper amperage scale and clamp the meter

probe around the wire to the “C” terminal of the compres-

sor. Turn on the unit and read the running amperage on

the meter. If the compressor does not start, the reading

will indicate the locked rotor amperage (L.R.A.).

external Overload

The compressor is equipped with an external overload

which senses both motor amperage and winding tem-

perature. High motor temperature or amperage heats the

overload causing it to open, breaking the common circuit

within the compressor.

Heat generated within the compressor shell, usually due

to recycling of the motor, is slow to dissipate. It may take

anywhere from a few minutes to several hours for the

overload to reset.

Checking the external Overload

With power off, remove the leads from compressor termi-

nals. If the compressor is hot, allow the overload to cool

before starting check. Using an ohmmeter, test continu-

ity across the terminals of the external overload. If you

do not have continuity; this indicates that the overload is

open and must be replaced.

Certain unit components operate at

temperatures hot enough to cause burns.

Proper safety procedures must be followed,

and proper protective clothing must be

worn.

Failure to follow this warning could result

in moderate to serious injury.

WARNING

BURN HAZARD

ELECTRIC SHOCK HAZARD

WARNING

Turn off electric power before service or

installation. Extreme care must be used, if it

becomes necessary to work on equipment

with power applied.

Failure to do so could result in serious injury or

death.