Hardware connections – FieldServer NCA2-NFS2-3030 User Manual

Page 4

Advertising
background image

FS-8700-130 Notifier NCA2/NFS-3030 Manual

Page 4 of 21

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]

3

HARDWARE CONNECTIONS

The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection
drawing.

Configure the Notifier Panel according to manufacturer’s instructions.

FieldServer

FieldServer Part #

8917-16

Pigtail for RJ45

Port

RJ45

Connection to TB5 Printer

Port.

Notifier NCA2/NFS2-3030

Connect to one of the RS-232

Ports on the FieldServer

P1

CTX CRX REF

PTX PRX REF

TB5

Printer

CRT

Rx (Brown)

Tx (Orange/White)

Com (Blue/White)

1

8

Connector Pinouts

TB5 CRT

Function Receive

Reference

Transmit

Pin

CRX

REF

CTX

TB5 Printer

Function Receive

Reference

Transmit

Pin

PRX

REF

PTX

RJ-45

Function Transmit

Com

Receive

Pin

8

4

1

Wire Color

Orange/white Blue/white Brown