FS-8700-130 Notifier NCA2/NFS-3030 Manual

Page 8 of 21

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]

Parameter

Addresses

For each SLC loop per Node

Memory Type : Detector ; Module

Fire Alarm

1 – 159

Security Life

160 – 318

Life Critical

319 – 477

Medical Emergency

478 – 636

Security Alarm

637 – 795

Critical Process

796 – 954

Supervisory

955 - 1113

Disabled

1114 – 1272

Prealarm

1273 – 1431

Active

1432 – 1590

ON/OFF

1591 – 1749

Memory Type : Detector_Trouble; Module_Trouble

Troubles/Faults

1 – 159

Parameter

Addresses

For each Node

Memory Type : Node_Trouble

Troubles/Faults

1 – 508

Memory Type : Panel

Panel

(Maximum12 Boards and 8 Panel circuits per Board )

Hardware address memory address
Board 1 panel 1 1
Board 1 panel 2 2
Board 2 panel 1 9
-----
-----
Board 12 panel 8 96
)

Fire Alarm

1 – 96

Security Life

97 - 192

Life Critical

193 - 288

Medical Emergency

289 - 384

Security Alarm

385 - 480

Critical Process

481 - 576

Supervisory

577 - 672

Disabled

673 - 768

Prealarm

769 - 864

Active

865 - 960

ON/OFF

961 - 1056

Memory Type : Panel_Trouble

Troubles/Faults

1–96

Memory Type : Bell_Trouble

Troubles/Faults

1-4

Table 1 – Memory Mapping Address Structure.