5.2

Client Side Connection Parameters

Section Title
Connections
Column
Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8

1

Protocol

Specify protocol used

nfs2-nca; nca2; nfs2-3030

Baud*

Specify baud rate

CRT Port
4800; 9600; 19200; 38400; 57600; (Vendor
limitation)
Printer Port
9600 (Vendor limitation)

Parity*

Specify parity

None (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

1 (Vendor limitation)


Example

// Client Side Connections

Connections
Port , Protocol , Baud , Stop_Bits , Parity
P8

, nfs2-nca , 9600 , 1

, None

5.3

Client Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric characters

Node_ID

Station address of any physical Node on
network

1-240. Set unique Id for standalone Notifer-
3030 Panel

Protocol

Specify protocol used

nfs2-nca or nca2 ; nfs2-3030

Port

Specify which port the device is connected
to the FieldServer

P1-P8


Example

// Client Side Nodes

Nodes

Node_Name , Node_ID , Protocol , Port
Panel_1

, 2

, nfs2-nca ,P8

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.