The USGF is specifically designed for heavy restaurant grease
and food service applications. These fans are UL and cUL Listed
for grease removal and have been tested under high temperature
(400° F) and abnormal flare-up (600° F) conditions.
Due to high temperatures and grease-laden airstreams in
commercial kitchen ventilation, system designers must be aware
of governing codes and guidelines. The National Fire Protection
Association (NFPA) is the primary source upon where many
codes for commercial kitchens ventilation are based. Selected
information from NFPA is shown below. Local code authorities
should be consulted before proceeding with any kitchen
ventilation project.
Exhaust fans used in kitchen ventilation applications must have
external wiring. (Wiring must not be installed in airstream.)
Installation must include a means for inspecting, cleaning and servicing the exhaust fan.
(e.g. Hinged Curb Cap)
No dampers are to be installed in the system.

W

all Opening

Damper Frame Size

Damper Size

Mounting Hole Bolt Cir

cl

e

Welded Duct

by Others

Recommended

Wall Opening

Mounting

Bolt Hole

Circle

Wall

Liquid Tight

Flexible Conduit

by Others

Welded Duct

by others

min. of 18 in.

above roof

deck per

NFPA

NEMA 3R

Disconnect

factory wired

from motor to

disconnect

through the

breather tube

(Optional)

Liquid Tight

Flexible Conduit

by Others

Recommended

Roof Opening

Roof Deck

Minimum 40"

Discharge

Height

8"min.

Grease

Trap

Vented Curb

Extension

External Wiring

External Wiring

Our Hoods and Filters.

Grease Grabber™
dual filtration system
works with the
Grease-X-Tractor™
filter to remove 80%
of the grease from
the kitchen exhaust.
Available in stainless
steel.

The Grease-X-
Tractor™ high
efficiency filter has
twice the grease
extraction capability
of a baffle filter.
Available in aluminum
or stainless steel.

Greenheck’s
Performance
Enhancing Lip
(PEL) helps direct
air to the filter and
improves capture and
performance

Full length, fully welded
integral grease trough

An integral 3-inch
airspace that meets
NFPA 96 clearance
requirements against
limited combustibles

Constructed of 304 /
430 18 ga. stainless
steel.

Standing seam
construction for added
strength

Redesigned flat light
panels allows for lights
to be installed vertically
and simplified field
installation

Fully welded joints - no
caulk

1

2

3

4

5

6

7

1

2

3

5

6

4

7

The high velocity
cartridge filters
offers dry cartridge
performance at
a lower cost.
Available in
aluminum or
stainless steel.

Baffle type filters
are the traditional
choice for
inexpensive grease
removal. Available
in aluminum,
stainless steel, or
non-stick coated.