Typical anchoring, Model number code, Usgf - 140 hp - 5 – Greenheck Fan USGF User Manual

Page 9: Metal building/steel deck anchoring, Wood deck anchoring, Corner detail, Configuration motor hp, Fan size, Pressure level

Advertising
background image



Typical Anchoring

Model Number Code

The Model number system is designed to completely identify the fan. The correct code letters must be
specified to designate the correct configuration. The remainder of the model number is determined by the
size and performance selected from the following pages.

USGF - 140 HP - 5

Configuration

Motor HP

U

ltimate

S

teel

G

rease

F

an

4

=

1

4

10

= 1

30

= 3

3

=

1

3

15

= 1

1

2

50

= 5

Fan Size

5

=

1

2

20

= 2

75

= 7

1

2

10

through

00

7

=

3

4

Pressure Level

HP

- High Pressure Wheel

XP

- Extended High Pressure Wheel

Metal Building/Steel Deck Anchoring

USGF

Size

Fan Curb Cap

Roof Opening

Fasteners Per Side

Outside Flange

141 - 161

22 x 22 (559 x 559)

181/2 x 181/2 (470 x 470)

5

31 x 31 (787 x 787)

180 - 200

30 x 30 (762 x 762)

201/2 x 201/2 (521 x 521)

7

39 x 39 (991 x 991)

All dimensions in inches (millimeters).

Roof Opening

Minimum 12 ga Steel

Roof Truss

Outside Flange

Center fasteners

on flange

Use #12-14 self-drilling screws or equal.
Fasteners one on each corner as detailed.
Each side at center of unit. Maximum

fastener spacing of 8 in. (203 mm), add

additional fasteners to satisfy.

Corrugated Roof Deck

5 in. (127 mm) Mounting Flange

1 in. (25 mm) Insulation

Outside of Roof Curb

1 in. (25 mm) less than

Fan Curb Cap

H-GPF Curb Height

8 to 18 in. (203 to 457 mm)

(Optional 24 in. (610 mm) SD Curb)

Corner Detail

11/4 in. (32 mm)

11/4 in.

(32 mm)

Wood Deck Anchoring

USGF

Size

Fan Curb Cap

Roof Opening

Fasteners Per Side

Outside Flange

140 - 160

22 x 22 (559 x 559)

181/2 x 181/2 (470 x 470)

7

31 x 31 (787 x 787)

180 - 200

30 x 30 (762 x 762)

201/2 x 201/2 (521 x 521)

7

39 x 39 (991 x 991)

All dimensions in inches (millimeters).

Roof Opening

Center fasteners

on flange

Outside Flange

Use #12 Wood Screws or equal into

minimum No. 1/No. 2 Southern Pine wood

support.
Fasteners one on each corner as detailed.
Each side at center of unit. Maximum

fastener spacing of 6 in. (152 mm), add

additional fasteners to satisfy.

Wood Support Member

Nominal 2 x 4, 6, 8

Wood Decking

2 in. (51 mm) Minimum Embedment

5 in. (127 mm) Mounting Flange

1 in. (25 mm) Insulation

H-GPF Curb Height

8 to 18 in. (203 to 457 mm)

(Optional 24 in. (610 mm) SD Curb)

Outside of Roof Curb

1 in. (25 mm) less than

Fan Curb Cap

Corner Detail

11/4 in. (32 mm)

11/4 in.

(32 mm)

Advertising