Typical installation and anchoring, Typical mounting - fan to curb, Concrete deck anchoring – Greenheck Fan USGF User Manual

Page 8: Corner detail

Advertising
background image



Typical Installation and

Anchoring

Concrete Deck Anchoring

USGF

Size

Fan Curb Cap

Roof Opening

Fasteners Per Side

Outside Flange

141 - 161

22 x 22 (559 x 559)

181/2 x 181/2 (470 x 470)

5

31 x 31 (787 x 787)

180 - 200

30 x 30 (762 x 762)

201/2 x 201/2 (521 x 521)

7

39 x 39 (991 x 991)

All dimensions in inches (millimeters).

Corner Detail

11/4 in. (32 mm)

11/4 in.

(32 mm)

Minimum Concrete

Strength of 2000 PSI

1 in. (25 mm) Insulation

Roof Opening

5 in. (127 mm) Mounting Flange

Outside Flange

Center fasteners

on flange

Use 3/8 in. (10 mm) expansion anchor

or equal into concrete.
Fasteners one on each corner as

detailed.
Each side at center of unit. Maximum

fastener spacing of 8 in. (203 mm),

add additional fasteners to satisfy.

Minimum 1-3/4 in. (44 mm)

edge distance

2-1/2 in. (64 mm)

Embedment Recommended

minimum 1-5/8 in. (41 mm)

CONCRETE DECK ANCHORING DETAIL

H-GPF Curb Height

8 to 18 in. (203 to 457 mm)

(Optional 24 in. (610 mm) SD Curb)

Outside of Roof Curb

1 in. (25 mm) less than Fan Curb Cap

Typical Mounting - Fan to Curb

USGF

Size

Fasteners

Per Side

Total

Fasteners

140 - 160

5

20

180 - 200

5

20

Fasteners on each side of the
fan are to be installed with one
fastener 4 in. (102 mm) from each
edge and one fastener centered.
The remaining fasteners are to be
equally spaced.

1/4 in. (6 mm) fastener minimum

5/16 in. (8 mm) recommended

See table for fastener quantities

FAN TO CURB MOUNTING DETAIL

H-GPF or SD curb

Fastener 4 in. (102 mm)

from curb edge