PMCS Interface Toolkit

Configuring and Using PMCS Wizards

45

Each "Alarm indicator" as defined by the Event Logger will appear to CIMPLICITY
as a DDE Integer item which can have the following values/states:

State

Tag
Value

Default
Color

Normal (no alarm)

10 - 19

Solid Gray

Alarm Active - Unacknowledged

20 - 29

Red Blinking

Alarm Active - Acknowledged

30 - 39

Solid Red

Alarm Reset - Unacknowledged
(alarm occurred but later went off before being
acknowledged)

40 - 49

Solid Yellow

Alarm Disabled
(Event Logger has disabled this alarm indicator)

0

Dark Gray

Each panel button displays one of five different colors, based on the states defined
above. A fill color animation link controlled by an indirect integer tag is used to
change colors. The fill color link is set as follows:

<= 9: Dark Grey

10 -> 19: Grey

20-> 29: Grey (will also have a flashing Red animation link)

30 -> 39: Red

>= 40: Yellow