Multiquip MQPower Whisperwatt Series DCA-300SSK User Manual

Page 25

Advertising
background image

DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD)— REV. #4 (03/27/06) — PAGE 25

120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R)
recepacles provided on the output terminal panel. These
receptacles can be accessed in any

voltage change-over

board position. Each receptacle is protected by a 20 amp
circuit breaker. These breakers are located directly above
the GFCI receptacles. Remember the load output (current)
of both GFCI receptacles is dependent on the load
requirements of the UVWO terminals.

Pressing the

reset button resets the GFCI receptacle after

being tripped. Pressing the "

Test Button" (See Figure 9) in

the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.

Figure 9. G.F.C.I. Receptacle

Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the GFCI
receptacles. Remember the load output (current) on all three
receptacles is dependent on the load requirements of the
UVWO terminals.

Turn the

voltage regulator control knob (Figure 11) on the

control panel to obtain the desired voltage. Turning the knob
clockwise will

increase the voltage, turning the knob counter-

clockwise will

decrease the voltage.

Figure 10. 240/139 VAC Twist-Lock

Auxiliary Receptacles

DCA-300SSK SERIES — OUTPUT TERMINAL PANEL FAMILIARIZATION

Twist Lock Dual Voltage 240/139 VAC Receptacles
There are three 240/139 VAC, 50 amp auxiliary twist-lock
(CS-6369) receptacles (Figure 10) provided on the output
terminal panel. These receptacles can be accessed in any
voltage change-over board
position.

Figure 11. Voltage Regulator Control Knob