Multiquip MQPower Whisperwatt Series DCA-300SSK User Manual

Page 41

Advertising
background image

DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD)— REV. #4 (03/27/06) — PAGE 41

DCA-300SSK SERIES — GEN. START-UP PROCEDURE (AUTO MODE)

When starting generator in AUTO mode use the "

Manual

Start-up" procedure except where noted (see below).

1. Before attempting to start generator, reference steps

1 thru 5 in the “

Before Starting Section” for Engine

Operating Panel S/N 3701673 and below.

2. Set the

battery ON/OFF switch (Figure 64) to the “ON

position.

Figure 65. Engine Speed Switch (High)

Figure 66. Off/Manual Auto Switch (AUTO)

4. Place the Off/Manual/Auto switch (Figure 66) on the

MPEC unit to the AUTO position.

Figure 64. Battery ON/OFF Switch

3. Set the engine speed switch (Figure 65) to the “High

position.

5. Continue operating the generator as outlined in steps 11

thru 19 in the “

Before Starting Section” for Engine

Operating Panel S/N 3701673 and below.

When the generator is set in the
AUTO mode, the generator will
automically start in the event of
comercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.

NOTE

Starting (Auto Mode)

Before connecting this generator to any
building’s electrical system, a

licensed

electrician must install an isolation
(transfer)
switch. Serious damage to the
building’s electrical system may occur
without this transfer switch.

DANGER - ELECTRICAL SYSTEM HAZARDS

When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

CAUTION - BACKUP GENERATOR USE

When running the generator in the AUTO mode, remember
the generator can start up at any time without warning.
NEVER attempt to perform any maintenance when the
generator is in the auto mode.

WARNING - AUTO MODE MAINTENANCE

When the MPEC

Control Switch

is placed in the AUTO position,
the engine glow plugs will be
warmed and the engine will start
automatically.

NOTE

CAUTION - ENGINE SPEED SWITCH

The

Engine Speed Switch must be set to the “High

position when running in the

Auto-Start mode. Failing to

set the switch in the proper position can result in damage
to your generator when it turns on.

Advertising