PAGE 36 — DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD) — REV. #4 (03/27/06)

DCA-300SSK SERIES — PRE-SETUP

When connecting battery do the following:

1. NEVER connect the battery cables to the battery

terminals when the

ignition switch is in either the Pre-

Heat, RUN, or START position. ALWAYS make sure
that the ignition switch is in the STOP position when
connecting the battery.

2. Place a small amount of battery terminal treatment

compound around both battery terminals. This will ensure
a good connection and will help prevent corrosion around
the battery terminals.

Figure 39. Battery Connections

Alternator
The polarity of the alternator is negative grounding type. When
an inverted circuit connection takes place, the circuit will be
in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water
into the alternator leads an electrolyte corrosion causing an
alternator failure.

Before charging the battery with an external electric source,
be sure to disconnect the battery cables.

Wiring
Inspect the entire generator for bad or worn electrical wiring
or connections. If any wiring or connections are exposed
(insulation missing) replace wiring immediately.

Piping and Hose Connection
Inspect all piping, oil hose, and fuel hose connections for
wear and tightness. Tighten all hose clamps and check hoses
for leaks.

If any hose (

fuel or oil) lines are defective replace them

immediately.

If the battery cable is connected
incorrectly, electrical damage to
the generator will occur. Pay close
attention to the polarity of the
battery when connecting the
battery.

NOTE

Battery
This unit is of negative ground DO NOT connect in reverse.
Always maintain battery fluid level between the specified
marks. Battery life will be shortened, if the fluid level are not
properly maintained. Add only distilled water when
replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables
are loose. Poor contact may result in poor starting or
malfunctions.

Always keep the terminals firmly tightened.

Coating the terminals with an approved battery terminal
treatment compound. Replace battery with only
recommended type battery.

The battery is sufficiently charged if the specific gravity of
the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
dead and needs to be recharged or replaced.

Battery Cable Installation
ALWAYS
be sure the battery cables (Figure 39) are properly
connected to the battery terminals as shown below. The
RED cable is connected to the positive terminal of the battery,
and the BLACK cable is connected to the negative terminal
of the battery.

Inadequate battery connections may cause poor starting
of the generator, and create other malfunctions.

CAUTION - BATTERY SERVICING SAFETY

If applicable perform the following:

■ Apply commercial power to the internal battery charger

receptacle (to ensure good starting) via commercial power.
An external power cord will be required. This capability is an

option

.

■ Apply commercial power to the jacket water heater

receptacle (not necessary for warm climates) via commercial
power. An external power cord will be required. This capability
is an

option

.

ALWAYS disconnect the negative terminal FIRST and
reconnect negative terminal LAST.

CAUTION - BATTERY SERVICING SAFETY