MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI
ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-6

FIGURE 1.2 Single Line Diagram - Bypass Operation. Load fed through static bypass line.

Referring to Figure 1.2, the Internal Static Bypass line is a Hard wired line through CB3 which

supplies the critical load with unconditioned input power. The purpose of this line is to route power

to the critical load while the UPS module is de-energized (converter and inverter), and during

Start-up before the system is fully operational.

The internal control system determines the operation of the two paths, with the load powered from

the inverter being the normal operation.

Referring to Figure 1.3, if the input power is interrupted, the battery will immediately supply the DC

power required by the Inverter to maintain continuous AC power to the load. A fully charged battery

will provide power for the specified time at the rated load, or longer at reduced load.

When power is restored after a low battery shutdown, the Converter automatically restarts operation,

recharges the batteries and the Inverter is automatically restarted without operator intervention. The

load is assumed by the inverter automatically without operator intervention.

In the event of a power failure, the Converter will de-energize and the batteries will discharge into

the Inverter and maintain power to the critical load until a) the battery capacity expires and the

inverter turns off, or b) input power is restored after which the converter will power the inverter and

simultaneously recharge the batteries. Figure 1.3 illustrates the flow diagram during battery

operation.

Maintenance
Bypass
Switch

FB

BATTERY

CB2

CB3

Static Transfer

Switch

Power Flow

Not in Use

Output

52C

CB1

FI

FO

AC input

CB

User
supplied

CONVERTER

INVERTER

UPS Module

40kVA, 50kVA:
External Battery

52CS(7.5-20kVA)
52MB&52L(30-50kVA)