OWNERS / TECHNICAL MANUAL

Page Number:

2-6


A) Output Contacts (for external alarm annunciation)

Output contacts consist of form “A” dry type contacts. The rated capacity of all output

contacts is 120Vac/0.5Aac or 30Vdc/1Adc. All dry contacts must be operated at their

rated values or lower. Figure 2.7 illustrates a typical installation. The external relay can

also be a lamp, LED, or computer, etc.

FIGURE 2.7 Control Wiring for External Contacts












Details of output alarm contacts :

Terminals 5 to 6

“Summary Alarm” contact

Activated when a fault alarm occurs.

Terminals 7 to 8

“Load on Inverter” contact

Activated when the power is supplied by the inverter.

Terminals 9 to 10

“Load on Bypass” contact

Activated when the power is supplied by the static bypass input.

Terminals 11 to 12 “Battery Operation” contact

Activated when the battery is operating following an AC power failure.

Terminals 13 to 14 “Converter Operation” contact

Activated when the converter is operating.

Terminals 15 to 16 “Battery Low Voltage” contact

Activated when battery voltage drops below discharge end voltage level during

inverter operation (i.e. During AC failure conditions).

Terminals 17 to 18 “Overload” contact

Activated when a system overload occurs.

User supplied

Terminal

UPS Cabinet

External to UPS
Cabinet

Relay

Coil

Power
Source

Relay

Contact

Terminal