2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-2

MITSUBISHI ELECTRIC 2033C SERIES UPS





This UPS does not include an AC input circuit breaker (MCCB) to protect the
bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field
supplied and installed. Circuit breaker (MCCB) specifications are as follows:

Capacity

(kVA)

AC input

Voltage (Vac)

AC input

Rating (Aac)

Recommended

Breaker (A)

7.5 208 23 30

10 208 30 35
15 208 45 60
20 208 61 75
30 208 91 125
40 208 121 150
50 208 151 200


AC output and DC input overcurrent protection and disconnection devices shall be field
supplied and installed.


















WARNING 2