MITSUBISHI ELECTRIC 2033C User Manual

Page 13

Advertising
background image


MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI
ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-7

FIGURE 1.3 Single Line Diagram - Battery Operation

The UPS is equipped with an internal rotary type Maintenance Bypass Switch (MBS) that can be

used to divert utility power to the load during maintenance sessions. Figure 1.4 illustrates the power

path when the MBS is in the BYPASS mode.

FIGURE 1.4 Single Line Diagram - UPS on Maintenance Bypass Operation.

(7.5/10/15/20kVA)

The rotary maintenance bypass switch is shown as 52CS in Figure 1.4. 52CS is a two position

three point make-before-break transfer switch.

(30/40/50kVA)

Two contactors (52MB, 52L) are used instead of the 52CS. A rotary switch(SWM) is used for

control of the two contactors.

UPS Module

FB

BATTERY

CB2

CB3

Static Transfer

Switch

Power Flow

Not in Use

Output

52C

CB1

FI

FO

AC input

CB

User
supplied

CONVERTER

INVERTER

Maintenance
Bypass
Switch

40kVA, 50kVA:
External Battery

52CS(7.5-20kVA)
52MB&52L(30-50kVA)

UPS Module

FB

BATTERY

CB2

CB3

Static Transfer

Switch

Power Flow

Not in Use

52C

FO

CONVERTER

INVERTER

Output

AC input

CB

User
supplied

Maintenance
Bypass
Switch

CB1

FI

40kVA, 50kVA:
External Battery

52CS(7.5-20kVA)
52MB&52L(30-50kVA)