Audible annunciator: [1] intermittent sound, [2] continuous sound.

(Note 2)

- "Major" is defined as a major failure. Load transferred from inverter to the static

bypass line;

-

"Minor" is defined as a minor failure. UPS continues to operate normally, but cause of

alarm must be identified;

-

“Over" is defined as an overload condition. Load will transfer from inverter to the static

bypass line and may or may not return to the inverter. Return to inverter will occur only

if overload corrects itself and output load is within rating of UPS. (Note: Inverter may

need to be restarted manually subsequent to an output bolted fault.)

(Note 3)

Indicates one of two possible LED illumination patterns - continuously on (lit) or

intermittent (flicker).