MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI
ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-15


TABLE 1.3 Detail of Specifications

Rated Output kVA

7.5

10

15

20

30

40

50

Rated Output kW

6

8

12

16

24

32

40

AC INPUT CHARACTERISTICS

Configuration

3 phase, 4 wire

Voltage

120/208 V +15% ~ -25%

Frequency 60

Hz

+/-

5%

Reflected Current THD

4% typ. at 100% load; 7% typ. at 50% load

BATTERY

Type VRLA
Ride Through
(at 100% load)

8min. 5min. 11min. 7min. 5min.

Nominal Voltage

360 Vdc

Minimum Voltage

300 Vdc

Number of Cells

180

AC OUTPUT

Configuration

3 phase, 3 or 4 wire

Voltage 120/208

V

Voltage Stability

+/-

1%

Frequency 60

Hz

Frequency Stability

+/-

0.01% in free running mode

Power Factor

0.8 nominal

Power Factor range

0.8 ~ 1.0 lagging (within output kW rating)

Voltage THD

2% typical THD at 100% Linear Load
4% typical THD at 100% non-linear load

Transient Response

+/-

3% typical at 100% load step

+/-

1% typical at loss/return of AC power

+/-

3% typical at load transfer to/from static bypass

Transient Recovery

16.7 ms

Voltage Unbalance

2% typical at 100% unbalanced load

Phase Displacement

1deg. typical at 100% load

Inverter Overload

150% for 1 minute

System Overload

150% for 1 minute, 1000% for 1 cycle (with bypass available)

Bypass Overload

150% for 1 minute, 1000% for 1 cycle

Crest Factor Capabilities 3:1

ENVIRONMENTAL

Cooling Forced

Air

Operating Temperature

32゚F ~ 104゚F (0゚C ~ 40゚C).
Recommended 59゚F ~ 77゚F (15゚C ~ 25゚C)

Relative Humidity

5% ~ 95% Non Condensing

Altitude

0 ~ 5000 feet No De-rating

Location

Temperature-controlled, indoor area free of conductive contaminants